Process data transfer

Process data serve to control the device.
–
The process data is transferred cyclically between the IO-Controller and the IO-Devices participating in PROFINET.
 
–
The process data can be directly accessed via the IO Controller. The data in the PLC, for instance, are directly stored in the IO area.
 
–
The maximum length of the process data is 1 ... 1440 bytes per direction.
 
–
The maximum number of PDO slots is 244 per direction with a maximum of 250 bytes within the slot.
 
–
The process data is transmitted 1 : 1 according to its sequence.
 
Example for 64 PDO slots:
–
1440 - ((64 slots * 2 bytes) + 4 bytes) = 1308 bytes of user data
 
Example for 244 slots:
–
1440 - ((244 slots * 2 bytes) + 4 bytes) = 948 bytes of user data