PROFINET IO-Device diagnostics

The following parameters show information on the network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2382:001
Active PROFINET settings: IP address
–
Read only
 
Display of the active IP address.
0x2382:002
Active PROFINET settings: Subnet
–
Read only
 
Display of the active subnet mask.
0x2382:003
Active PROFINET settings: Gateway
–
Read only
 
Display of the gateway address.
0x2382:004
Active PROFINET settings: Station name
–
Read only
 
Display of the active station name.
0x2382:005
Active PROFINET settings: MAC Address
–
Read only
 
Display of the active MAC address.
0x2388
PROFINET status
–
Read only
 
Bit coded display of the current Bus status.
Bit  0
Initialized
Bit  1
Online
Bit  2
Connected
Bit  3
IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
Bit  4
Hardware fault
Bit  5
Reserved
Bit  6
Watchdog elapsed
Bit  7
Protocol error
Bit  8
PROFINET stack ok
Bit  9
PROFINET stack not configured
Bit  10
Ethernet controller fault
Bit  11
UDP stack fault
0x2389:001
PROFINET error: Error 1
–
Read only
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:002.
 
0
No error
2
Unit ID unknown
3
Max. units exceeded
4
Invalid size
5
Unit type unknown
6
Runtime plug error
7
Invalid argument
8
Service pending
9
Stack not ready
10
Command unknown
11
Invalid address descriptor
0x2389:002
PROFINET error: Error 2
–
Read only
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:001.
 
Bit  7
IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
Bit  8
Station name problem
The station name must be assigned according to the PROFINET specification.
Bit  9
DataExch left
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e. g. by cable break.
–
PROFINET communication changes to the "No_Data_Exchange" state.
 
–
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in is triggered in the device.
 
Bit  10
Stack boot error
Bit  11
Stack online error
Bit  12
Stack state error
Bit  13
Stack revision error
Bit  14
Initialization problem
The stack cannot be initiated with the user specifications. A reason might be, e. g., a station name that does not correspond to the PROFINET specification.
Bit  15
Stack init error