EtherCAT state machine

Before communication via EtherCAT is possible, the fieldbus scans the EtherCAT state machine when booting. The following illustration shows the possible state change from the point of view of an EtherCAT slave:
Fig. 1: EtherCAT state machine
 
State
Description
Init
–
Initialization phase
 
–
No SDO/PDO communication with the slaves
 
–
Device can be detected by fieldbus scan
 
Pre-operational
–
The fieldbus is active.
 
–
SDO communication (mailbox communication) is possible.
 
–
No PDO communication
 
Safe-operational
–
SDO communication (mailbox communication) is possible.
 
–
PDO communication:
 
–
The input data in the process image is updated.
 
–
The output data from the process image is not transferred to the slaves.
 
 
Operational
Normal operation
–
SDO communication
 
–
PDO communication
 
–
Fieldbus synchronization has been successful (if used)
 
 
 
A fieldbus scan is possible in any EtherCAT state.
The SDO communication via the EtherCAT bus is only possible if at least the "Pre-Operational" state has been reached.
 
 
AL status code
Possible errors during transitions between states are entered in the EtherCAT register of the concerned slave in AL Status Code (address 0x0134:0x0135).
Often indicated AL status code [hex]
Description
0x0000
No error
0x0011
Invalid status change requested
0x0012
Unknown status requested
0x0013
Bootstrap status is not supported
0x0016
Invalid mailbox configuration Pre-Operational
0x001A
Synchronization error
0x001B
Sync manager watchdog
0x001D
Invalid output data configuration
0x001E
Invalid input data configuration
0x002B
Invalid input and output data
0x0030
Invalid configuration of DC synchronization
0x9001
Firmware watchdog error
0x9002
Mapping error