0x2362:007
|
Active EtherCAT settings: Tx length
|
Display of the length of the transmitted cyclic data in bytes.
A value other than zero is only displayed if the master / slave process data is configured correctly.
|
|
0x2362:008
|
Active EtherCAT settings: Rx length
|
Display of the length of the received cyclic data in bytes.
A value other than zero is only displayed if the master / slave process data is configured correctly.
|
|
0x2368
|
EtherCAT status
|
Display of the current network status.
|
|
0
|
No EtherCAT module
|
|
|
1
|
Initialization
|
Network initialization is active.
|
|
2
|
Pre-Operational
|
The network is active.
|
|
3
|
Bootstrap
|
Firmware update active.
|
|
4
|
Safe-Operational
|
–
SDO transmission (CoE communication via mailbox) is possible.
–
PDO transmission: – The input data in the process image are updated. – The output data from the process image are not transmitted.
|
|
8
|
Operational
|
Normal operation
|
|
0x2369
|
EtherCAT error
|
|
|
Bit
0
|
Watchdog elapsed
|
The SyncManager watchdog has triggered.
|
|
Bit
2
|
Invalid configuration
|
The configuration sent by the EtherCAT master is invalid.
|
|
Bit
3
|
Stack init error
|
Internal error when initializing the interface.
|
|
Bit
4
|
Invalid process data
|
The flag indicates that the process data is invalid.
|