Basic setting
The following parameters must be set for the activation and basic configuration of the holding brake control.
When a power contactor is used, the response time and release time of the contactor
are added to the brake application and release time. Both times must also be taken
into consideration for parameterising the brake application time and brake opening time!
Deactivate automatic DC braking, if a holding brake is used.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2820:001
|
Holding brake control: Brake mode
–
Setting can only be changed if the inverter is disabled.
|
Selecting how the "Release holding brake" command is to be triggered.
|
|
|
0
|
Automatically (via device state)
|
"Automatic operation": The "Release holding brake" command is automatically carried out as a function of the device state and further conditions.
CAUTION!
In automatic operation, a manual release of the holding brake is also possible! For details see the following information for selection "Manually [1]".
|
|
|
1
|
Manually
|
The "Release holding brake" command can also be initiated by the following external triggers:
–
Via the trigger assigned to the "Release holding brake" function in 0x2631:049 if the network control is not active.
–
Via bit 14 in the CiA control word 0x6040 if the network control is active.
CAUTION!
–
The manually triggered "Release holding brake" command has a direct impact on the "Release holding brake [115]" trigger.
Thus, the holding brake can be manually released if the power section is switched off!
–
The ramp function generator only starts up when the brake is released in the case of manual control.
–
The responsibility for a manual release of the holding brake has the external trigger source for the "Release holding brake" command!
|
|
|
2
|
Off
|
The holding brake is deactivated.
|
|
|
0x2820:002
|
Holding brake control: Brake closing time
0 ... [100] ... 10000 ms
|
Application time (engagement time) of the holding brake.
–
Only effective in automatic operation.
|
|
|
0x2820:003
|
Holding brake control: Brake opening time
0 ... [100] ... 10000 ms
|
Release time (disengagement time) of the holding brake.
–
Only effective in automatic operation.
|
|
|
0x2820:015
|
Holding brake control: Brake status
–
Read only
|
Display of the holding brake status.
|
|
|
0
|
Brake closed
|
Holding brake is applied.
|
|
|
1
|
Brake released
|
Holding brake is released.
|
|
|
0x2820:023
|
Holding brake control: Control configuration
|
Selection of which output signal is to be used to control the holding brake.
|
|
|
0
|
Via internal brake module
|
The holding brake is controlled via the internal brake module (outputs X105/BD1+BD2 or X106/BD1+BD2).
–
An open-circuit detection is active.
–
A parameterized voltage reduction is active.
|
|
|
2
|
Via external module at DOx
|
The holding brake is controlled via the trigger "Release holding brake [115]".
–
This trigger must be assigned to a digital output. The digital output in turn controls a relay or power contactor which switches the brake supply.
–
The digital output is not suitable for direct control of a holding brake!
–
If, instead of an electrically releasing (self-holding) holding brake, an electrically holding (self-releasing) holding brake is to be controlled, a signal inversion must be set for the digital output used!
|
|
|
0x2820:024
|
Holding brake control: Rated voltage
–
Setting can only be changed if the inverter is disabled.
|
Rated voltage of the holding brake.
–
The rated voltage is indicated on the nameplate of the holding brake.
–
For Lenze geared motors, the default setting must be used.
|
|
|
2
|
104 VDC
|
||
|
4
|
180 VDC
|
||
|
6
|
205 VDC
|
||
|
7
|
215 VDC
|
||
|
0x2820:025
|
Holding brake control: Brake boost mode
|
Special boost settings for the rated voltage.
|
|
|
0
|
133% / 66%
|
||
|
1
|
133% / 83%
|
||
|
2
|
133% / 100%
|
||
|
3
|
100% / 100%
|
||
For examples and details on more possible settings, see the following subchapter:
–
–
–
–
CAUTION!
Configure digital outputs