Information on the network

Parameter
Address
Name / setting range / [default setting]
Information
0x2322:001
Active Modbus settings: Active node ID
–
Read only
 
Display of the active node address.
0x2322:002
Active Modbus settings: Active baud rate
–
Read only
 
Display of the active baud rate.
0
Automatic
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
57600 bps
7
115200 bps
0x2322:003
Active Modbus settings: Data format
–
Read only
 
Display of the active data format.
0
Automatic
Automatic data format detection.
–
With this setting, the first 5 ... 10 messages are lost after switch-on.
 
1
8, E, 1
8 data bits, even parity, 1 stop bit
2
8, O, 1
8 data bits, odd parity, 1 stop bit
3
8, N, 2
8 data bits, no parity bit, 2 stop bits
4
8, N, 1
8 data bits, no parity bit, 1 stop bit
0x232A:001
Modbus statistics: Messages received
–
Read only
 
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
 
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:002
Modbus statistics: Valid messages received
–
Read only
 
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:003
Modbus statistics: Messages with exceptions
–
Read only
 
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:004
Modbus statistics: Messages with errors
–
Read only
 
Display of the number of messages received with a faulty data integrity (parity, CRC).
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:005
Modbus statistics: Messages sent
–
Read only
 
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232E:001
Modbus diagnostics of last Rx data: Offset
0 ... [0] ... 240
For purposes of diagnostics, the last message received (max. 16 bytes) is shown in 0x232E:002...0x232E:017. For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232E:002
Modbus diagnostics of last Rx data: Data byte 0
–
Read only
 
Display of the message received last.
0x232E:003
Modbus diagnostics of last Rx data: Data byte 1
–
Read only
 
0x232E:004
Modbus diagnostics of last Rx data: Data byte 2
–
Read only
 
0x232E:005
Modbus diagnostics of last Rx data: Data byte 3
–
Read only
 
0x232E:006
Modbus diagnostics of last Rx data: Data byte 4
–
Read only
 
0x232E:007
Modbus diagnostics of last Rx data: Data byte 5
–
Read only
 
0x232E:008
Modbus diagnostics of last Rx data: Data byte 6
–
Read only
 
0x232E:009
Modbus diagnostics of last Rx data: Data byte 7
–
Read only
 
0x232E:010
Modbus diagnostics of last Rx data: Data byte 8
–
Read only
 
0x232E:011
Modbus diagnostics of last Rx data: Data byte 9
–
Read only
 
0x232E:012
Modbus diagnostics of last Rx data: Data byte 10
–
Read only
 
0x232E:013
Modbus diagnostics of last Rx data: Data byte 11
–
Read only
 
0x232E:014
Modbus diagnostics of last Rx data: Data byte 12
–
Read only
 
0x232E:015
Modbus diagnostics of last Rx data: Data byte 13
–
Read only
 
0x232E:016
Modbus diagnostics of last Rx data: Data byte 14
–
Read only
 
0x232E:017
Modbus diagnostics of last Rx data: Data byte 15
–
Read only
 
0x232F:001
Modbus diagnostics of last Tx data: Offset
0 ... [0] ... 240
For purposes of diagnostics, the last message sent (max. 16 bytes) is shown in 0x232F:002...0x232F:017. For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232F:002
Modbus diagnostics of last Tx data: Data byte 0
–
Read only
 
Display of the message sent last.
0x232F:003
Modbus diagnostics of last Tx data: Data byte 1
–
Read only
 
0x232F:004
Modbus diagnostics of last Tx data: Data byte 2
–
Read only
 
0x232F:005
Modbus diagnostics of last Tx data: Data byte 3
–
Read only
 
0x232F:006
Modbus diagnostics of last Tx data: Data byte 4
–
Read only
 
0x232F:007
Modbus diagnostics of last Tx data: Data byte 5
–
Read only
 
0x232F:008
Modbus diagnostics of last Tx data: Data byte 6
–
Read only
 
0x232F:009
Modbus diagnostics of last Tx data: Data byte 7
–
Read only
 
0x232F:010
Modbus diagnostics of last Tx data: Data byte 8
–
Read only
 
0x232F:011
Modbus diagnostics of last Tx data: Data byte 9
–
Read only
 
0x232F:012
Modbus diagnostics of last Tx data: Data byte 10
–
Read only
 
0x232F:013
Modbus diagnostics of last Tx data: Data byte 11
–
Read only
 
0x232F:014
Modbus diagnostics of last Tx data: Data byte 12
–
Read only
 
0x232F:015
Modbus diagnostics of last Tx data: Data byte 13
–
Read only
 
0x232F:016
Modbus diagnostics of last Tx data: Data byte 14
–
Read only
 
0x232F:017
Modbus diagnostics of last Tx data: Data byte 15
–
Read only