Information on the network
The following parameters show information on the network.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x23B2:001
|
Active Modbus TCP settings: Active IP address
–
Read only
|
Display of the active IP address.
|
|
|
0x23B2:002
|
Active Modbus TCP settings: Active subnet
–
Read only
|
Display of the active subnet mask.
|
|
|
0x23B2:003
|
Active Modbus TCP settings: Active gateway
–
Read only
|
Display of the active gateway address.
Example
The setting 276344004 corresponds to the gateway address 196.172.120.16.
–
276344004 = 0x1078ACC4
à 0xC4.0xAC.0x78.0x10 = 196.172.120.16 |
|
|
0x23B2:005
|
Active Modbus TCP settings: MAC address
–
Read only
|
Display of the active MAC address.
|
|
|
0x23B5:001
|
Active port settings: Port 1
–
Read only
|
Display of the baud rate set for Port 1 in 0x23B4:001.
|
|
|
0
|
Not connected
|
||
|
1
|
10 Mbps/Half Duplex
|
||
|
2
|
10 Mbps/Full Duplex
|
||
|
3
|
100 Mbps/Half Duplex
|
||
|
4
|
100 Mbps/Full Duplex
|
||
|
0x23B5:002
|
Active port settings: Port 2
–
Read only
|
Display of the baud rate set for Port 2 in 0x23B4:001.
|
|
|
0
|
Not connected
|
||
|
1
|
10 Mbps/Half Duplex
|
||
|
2
|
10 Mbps/Full Duplex
|
||
|
3
|
100 Mbps/Half Duplex
|
||
|
4
|
100 Mbps/Full Duplex
|
||
|
0x23B8
|
Modbus TCP module status
–
Read only
|
Display of the TCP module state.
|
|
|
0
|
Power off
|
||
|
1
|
Initialization
|
||
|
2
|
Warning
|
||
|
3
|
Fault
|
||
|
4
|
No configuration
|
||
|
5
|
Operational
|
||
|
0x23B9
|
Modbus TCP/IP network status
–
Read only
|
Display of the active network status.
|
|
|
0
|
No configuration
|
||
|
1
|
Initialization
|
||
|
2
|
Connection time-out
|
||
|
3
|
Configuration error
|
||
|
4
|
Not connected
|
||
|
5
|
Connection established
|
||
|
0x23BA:001
|
Modbus TCP statistics: Messages received
–
Read only
|
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:002
|
Modbus TCP statistics: Valid messages received
–
Read only
|
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:003
|
Modbus TCP statistics: Messages with exceptions
–
Read only
|
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:005
|
Modbus TCP statistics: Messages sent
–
Read only
|
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BE:001
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Receive offset
0 ... [0] ... 240
|
For diagnostic purposes, the last received message (max. 16 bytes) is displayed in 0x23BE:002. For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
|
|
|
0x23BE:002
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Rx message
–
Read only
|
Display of the message received last.
|
|
|
0x23BE:003
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Transmit offset
0 ... [0] ... 240
|
For diagnostic purposes, the last sent message (max. 16 bytes) is displayed in 0x23BE:004. For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
|
|
|
0x23BE:004
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Tx message
–
Read only
|
Display of the message sent last.
|
|