Parameter download

Parameter settings are not stored in a power failure safe manner when using the inverter as a system drive in the Lenze system. All inverter settings that deviate from the Lenze default setting are held centrally in the Lenze controller and saved there persistently. All parameters are transferred from the Lenze controller to the inverter during initialization upon start-up.
All size-dependent parameters are not downloaded.
 
The parameters of the inverter are managed in the »PLC Designer« project. The »PLC Designer« project, including the parameters, is saved on the engineering PC using the storage function of »PLC Designer«.The »PLC Designer« transfers the parameters to the Lenze controller when the controller is logged on to. The controller passes the parameter sets to the subordinate controller. The parameter sets are written back to the inverter by the Lenze controller every time the system starts.
There are three application for managing and modifying parameters:
–
Modifying the parameters of an inverter online:
 
–
If a parameter is modified online, the »PLC Designer« writes the parameter directly to the corresponding inverter and simultaneously modifies the parameter in the »PLC Designer«- project.
The parameter modification is not registered in the Lenze controller. The parameter modification in the inverter is lost when the controlleris cold-started. Log out and log back in again with the »PLC Designer« to avoid this. (Menu commands: Online → Log out / Online → Log in)
 
 
–
In this case, the complete parameter set is written to the controller and transferred to the inverter.
 
–
The parameter set is only available in the inverter and controller after the transfer by logging in until the system is next shut down (not stored in a power failure safe manner).
 
 
–
Modifying the parameters of an inverter offline:
 
–
If a parameter is modified offline, the »PLC Designer« modifies the value directly in the »PLC Designer« project. When logging into the Lenze controller, the complete parameter set is written to the controller. It then transfers the parameter set to the inverter.
 
–
The parameter set is only available in the inverter and controller after the transfer by logging in until the system is next shut down (not stored in a power failure safe manner).
 
 
–
Saving the parameters of the inverter in the Lenze controller so that they remain in the device after switching off:
 
–
A separate parameter set for the subordinate inverters is available in the boot project of the Lenze controller. It is only updated if the "Create boot project" function is executed via the »PLC Designer«. The current parameterisation is then saved and is available after the mains connection. The stored parameter set is automatically written to the inverter by the controller at boot-up following mains connection.
 
–
If a boot project exists on the Lenze controller, the parameters of the inverter can also be modified with »EASY Starter« and stored permanently.
 
 
Modifying parameters and permanently storing them.
1.
Open »EASY Starter«.
 
2.
Connect to the inverter online
 
3.
Modify desired parameters.
 
4.
Connect to the Lenze controller online.
 
5.
Select 'Safe parameter set in the device (F6)'.
The Lenze controller then starts uploading the parameters of all its EtherCAT slaves (including i550 EtherCAT) and stores these parameters together with its own parameter set in its boot project. The stored parameter set for the i550 EtherCAT is automatically written to the inverter by the controller when the Lenze controller powers up after mains connection.
If the modified parameter set from the inverter should correspond to the »PLC Designer« project:
 
6.
Log in to the Lenze controller.
 
7.
If the dialogue displays differences in the parameter selection, select Upload all.
 
8.
Save the »PLC Designer« project.