Restarting or stopping the communication

Restart or stop communication
The 0x2380 parameter can be used to restart or stop communication. Optionally, it is also possible to reset all communication parameters to the last saved state.
A restart of communication is required after changes of the interface configuration (e. g. station address and baud rate) in order that the changed settings become effective.
For restarting communication, there are two options:
1.
Switch inverter off and on again.
 
2.
Set 0x2380 = 1 (Restart with current values).
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2380
PROFINET communication
Restart / stop communication
–
When the device command has been executed successfully, the value 0 is shown.
 
0
No action/no error
Only status feedback
1
Restart with current values
Restart communication with the current values.
2
Restart with stored values
Restart communication with the values of the PROFINET parameters that have been saved last (0x2381:001 ... 0x2381:009).
10
In progress
Only status feedback
11
Action cancelled
12
Fault