Process data transfer
The process data is used to control the inverter.
–
The process data is transmitted cyclically between the IO-Controller and the IO-Devices participating in PROFINET.
–
The process data can be directly accessed by the IO controller. The data in the PLC, for instance, are directly stored in the I/O area.
–
The available 27 network registers ("slots") serve to maximally exchange 16 process data words (data types 8-bit or 16-bit) or 8 process data double words (data type 32-bit) for each direction.
–
Output data direction: From IO-Controller to IO-Device.
–
Input data direction: From IO-Device to IO-Controller.
Data mapping
Data mapping is used to define which process data is exchanged cyclically between IO-Controller and IO-Device.
–
If the inverter is known as IO-Device in the PROFINET network and the IO-Controller connects to the inverter for the first time, the mapping objects are automatically transmitted to the inverter.
–
Internal mapping of the process output data: 0x24E0:001 ... 0x24E0:016
–
Internal mapping of the process input data: 0x24E1:001 ... 0x24E1:016
All subsequent changes in the objects 0x24E0 and 0x24E1 can cause PROFINET alarms according to the deviation from the automatically set configurations.
RPDO mapping
The assignment of different bits with the same function is not permissible.
For the process data from the IO-Controller to the inverter, this data mapping is preset in the device description file:
1.
NetWordIN1 data word 0x4008:001
2.
Network setpoint frequency (0.01) 0x400B:005
|
Bit
|
Default setting
|
For details and configuration, see
|
|
0
|
Not active (reserve)
|
|
|
1
|
Not active (reserve)
|
|
|
2
|
Activate quick stop
|
|
|
3
|
Not active (reserve)
|
|
|
4
|
Run forward (CW)
|
|
|
5
|
Activate preset (bit 0)
|
|
|
6
|
Activate preset (bit 1)
|
|
|
7
|
Reset error
|
|
|
8
|
Not active (reserve)
|
|
|
9
|
Activate DC braking
|
|
|
10
|
Not active (reserve)
|
|
|
11
|
Not active (reserve)
|
|
|
12
|
Reverse rotational direction
|
|
|
13
|
Not active (reserve)
|
|
|
14
|
Not active (reserve)
|
|
|
15
|
Not active (reserve)
|
Specifying the frequency setpoint
–
The specification is made unsigned (independent of the direction of rotation) as integer in the resolution [0.01 Hz].
–
The direction of rotation is defined in the default setting via bit 12 of the NetWordIN1 data word.
–
Example: 4560 = 45.60 Hz
TPDO mapping
The assignment of different bits with the same function is not permissible.
For the process data from the inverter to the IO-Controller, the following data mapping is preset in the device description file:
1.
NetWordOUT1 data word 0x400A:001
2.
Frequency (0.01) 0x400C:006
3.
Motor current 0x2D88
|
Bit
|
Default setting
|
For details and configuration, see
|
|
0
|
Ready for operation
|
|
|
1
|
Not connected
|
|
|
2
|
Operation enabled
|
|
|
3
|
Fault active
|
|
|
4
|
Not connected
|
|
|
5
|
Quick stop active
|
|
|
6
|
Running
|
|
|
7
|
Device warning active
|
|
|
8
|
Not connected
|
|
|
9
|
Not connected
|
|
|
10
|
Setpoint speed reached
|
|
|
11
|
Current limit reached
|
|
|
12
|
Actual speed = 0
|
|
|
13
|
Rotational direction reversed
|
|
|
14
|
Release holding brake
|
|
|
15
|
Inverter disabled (safety)
|
Output of the actual frequency value
–
The output is made unsigned (independent of the direction of rotation) as integer in the resolution [0.01 Hz].
–
An active reversal is displayed via bit 13 of the NetWordOUT1 data word.
–
Example: 4560 = 45.60 Hz