Required commissioning steps

1.
Activate motor control type: 0x2C00 = "Sensorless control for synchronous motors (SLSM-PSM) [8]".
 
2.
Automatic motor identification (energized) 
 
–
Mandatory for this motor control mode in order to determine the equivalent circuit data and calculate the parameters for encoderless operation with HF injection.
 
 
3.
Optionally for a speed control with torque limitation in operating mode 0x6060 = "MS: Velocity mode [-2]":
 
–
Select the source in 0x2949:001 for the positive torque limit source and set it accordingly.
 
–
Select the source in 0x2949:002 for the negative torque limit source and set it accordingly.
 
 
4.
Optionally for a speed control with torque limitation in operating mode 0x6060 = "CiA: Velocity mode (vl) [2]":
 
–
Set the positive torque limit in 0x60E0
 
–
Set the negative torque limit in 0x60E1.