Preconditions
To activate the Safe Muting function, you need:
–
A PC with »EASY Starter« or »PLC Designer«.
–
A permanent communication link between the engineering tool and the inverter.
–
In a network, the Safe Muting function can only be activated for one inverter at a time.
–
A muting password was set using the password dialog in the parameterization dialog for safety parameters.
–
The active safe parameter set in the inverter must include the settings for Safe Muting:
–
The sources to be hidden.
–
The muting password.