Activation
To set the Safe Muting password (or change an existing password):
1.
Open the parameterization dialog for safety parameters:
a.
»EASY Starter«: Open the Safety parameter list tab.
b.
»PLC Designer«: In the device tree, under the axis, open the object Safety parameter set in the device tree under the axis.
2.
Click the " " button and execute the "Muting Password" command.
The "Change Muting Password" dialog box opens.
3.
Set the muting password.
4.
Transfer the safety parameters to the device so that the change to the muting password takes effect.
To activate and deactivate safe muting:
1.
Open parameterization dialog:
a.
»EASY Starter«: Open the Safety parameter list tab.
b.
»PLC Designer«: Open the Safety parameter set object under the axis in the device tree.
2.
Click on the button (hide input signals of the device).
The password dialog opens.
3.
Enter muting password.
The muting dialog opens.
4.
Use the displayed data to ensure that the correct inverter has been selected.
Optical device identification is activated automatically. The two LEDs "RDY" and "ERR" on the front of the selected inverter flash quickly.
5.
Start activates the function.
The function is now active for a maximum of 30 minutes. The remaining time is displayed.
6.
End function
Monitored operation is reactivated immediately.
All previously deactivated safety functions are active again.
All previously deactivated safety functions are active again.
a.
The function is automatically ended after 30 minutes.
b.
Stop ends the function manually.
c.
If the connection between the engineering tool and the inverter is disconnected, the function is terminated immediately with an error message.
" button and execute the "Muting Password" command.
(hide input signals of the device).