Setting

Reset muting password
The muting password can be reset in the Safety parameter list: 0x213B:001 (MUT: Password) = 0
 
Parameter
Address
Name / setting range / [default setting]
Information
0x213A:001
MUT: Mute S-Bus
–
Safety parameter (Safety parameter list)
 
Selection of sources to be hidden.
0
No muting
3
Mute completely
0x213A:002
MUT: Mute SD-In1
–
Safety parameter (Safety parameter list)
 
Selection of sources to be hidden.
0
No muting
1
Mute
0x213A:003
MUT: Mute SD-In2
–
Safety parameter (Safety parameter list)
 
Selection of sources to be hidden.
0
No muting
1
Mute
0x213A:016
MUT: Mute SD-In1-A
–
Safety parameter (Safety parameter list)
 
0
No muting
1
Mute
0x213A:017
MUT: Mute SD-In1-B
–
Safety parameter (Safety parameter list)
 
0
No muting
1
Mute
0x213A:018
MUT: Mute SD-In2-A
–
Safety parameter (Safety parameter list)
 
0
No muting
1
Mute
0x213A:019
MUT: Mute SD-In2-B
–
Safety parameter (Safety parameter list)
 
0
No muting
1
Mute
0x213B:001
MUT: Password
0 ... [0] ... 4294967295
–
Safety parameter (Safety parameter list)
 
Password to activate the function.
Enter "0" to reset the password.
0x213B:002
MUT: Remaining time
–
Read only: x s
 
Remaining time until the function is automatically terminated.
The function is active for a maximum of 30 minutes.
0x213C
MUT "MUT active" - Output
–
Safety parameter (Safety parameter list)
 
Selection of the safe output for the "MUT active" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic