Automatic firmware download with Lenze Controller
The firmware of the inverter can be saved together with the »PLC Designer«-project. During start-up, the Lenze controller checks whether the firmware version in the inverter corresponds with the firmware version stored in the project for this device. If this is not the case, the controller loads the firmware version stored in the project to the inverter. In doing so, a "device replacement" can be ensured for service purposes, whereby the replacement device also functions with the same firmware version stored in the project, as the original device did previously.
Main version check
An automatic firmware download from the PLC to the inverter is only undertaken under the following conditions:
–
Required firmware version 05.01.x.x or higher
–
Identical main version 05.01.x.x in the inverter and in the PLC project
–
Bootloader version 00.00.00.18 or higher
Main version check from firmware version 07.x.x.x
Restrictions as of firmware version 07.x.x.x:
–
There is no automatic firmware download if an inverter firmware version 07.x.x.x ("PLC Designer" project) has been stored on the Lenze controller and the replacement device contains firmware version 07.x.x.x in the "Device replacement" service case.
–
The EtherCAT network remains in the "Pre-Operational" status if an inverter firmware version 07.x.x.x ("PLC Designer" project) has been stored on the Lenze controller and the replacement device contains firmware version 07.x.x.x in the "Device replacement" service case.
To get out of the "Pre-Operational" status, a manual intervention is required. For detailed information, refer to the commissioning document of the Lenze controller.
To get out of the "Pre-Operational" status, a manual intervention is required. For detailed information, refer to the commissioning document of the Lenze controller.
Restrictions
Power failure during firmware download: iCIF connection lost [33200]
In the event of a power failure, the inverter switches to a fault state. There is then only one means for recovery:
–
Load the firmware using the Firmware-Loader via the USB diagnostic module.
–
Restart the inverter.
It may occur that the inverter switches to a fault state after a successful firmware download.
Behavior after successful firmware download: Network: interruption of cyclic data exchange [33169]
–
Acknowledge the error via »PLC Designer« ,»Easy Starter« or via the mains switch.
Engineering tool access during firmware download:
During the firmware download via the Controller, no simultaneous connection to an engineering tool shall be active (Easy Starter / PLC Designer). In the event of an error, the is only one way to restore the connection:
–
Load the firmware with the firmware loader via the USB diagnostic module.
–
Restart the inverter.