Information on the network

The following parameters serve to diagnose the communication activities between the inverter and the Modbus network.
 
The following parameters show information on the network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23B2:001
(P511.01)
Active Modbus TCP settings: Active IP address
(Act. MBTCP sett.: Act. IP address)
–
Read only
 
–
From version 04.00
 
Display of the active IP address.
0x23B2:002
(P511.02)
Active Modbus TCP settings: Active subnet
(Act. MBTCP sett.: Act. subnet)
–
Read only
 
–
From version 04.00
 
Display of the active subnet mask.
0x23B2:003
(P511.03)
Active Modbus TCP settings: Active gateway
(Act. MBTCP sett.: Act. gateway)
–
Read only
 
–
From version 04.00
 
Display of the active gateway address.
Example
The setting 276344004 corresponds to the gateway address 196.172.120.16.
–
276344004 = 0x1078ACC4
à
 0xC4.0xAC.0x78.0x10 = 196.172.120.16
 
0x23B2:005
(P511.05)
Active Modbus TCP settings: MAC address
(Act. MBTCP sett.: MAC address)
–
Read only
 
–
From version 04.00
 
Display of the active MAC address.
0x23B3
(P509.00)
Switch position
(Switch position)
–
Read only
 
–
From version 04.00
 
Display of the rotary encoder switch setting at the last mains power-on.
0x23B5:001
(P513.01)
Active port settings: Port 1
(Act. port sett.: Port 1)
–
Read only
 
–
From version 04.00
 
Display of the baud rate set for Port 1 in 0x23B4:001 (P512.01).
0
Not connected
1
10 Mbps/Half Duplex
2
10 Mbps/Full Duplex
3
100 Mbps/Half Duplex
4
100 Mbps/Full Duplex
0x23B5:002
(P513.02)
Active port settings: Port 2
(Act. port sett.: Port 2)
–
Read only
 
–
From version 04.00
 
Display of the baud rate set for Port 2 in 0x23B4:001 (P512.01).
0
Not connected
1
10 Mbps/Half Duplex
2
10 Mbps/Full Duplex
3
100 Mbps/Half Duplex
4
100 Mbps/Full Duplex
0x23B8
(P516.00)
Modbus TCP module status
(MBTCP modul. stat)
–
Read only
 
–
From version 04.00
 
Display of the TCP module state.
0
Power off
1
Initialization
2
Warning
3
Fault
4
No configuration
5
Operational
0x23B9
(P517.00)
Modbus TCP/IP network status
(MBTCP netw stat)
–
Read only
 
–
From version 04.00
 
Display of the active network status.
0
No configuration
1
Initialization
2
Connection time-out
3
Configuration error
4
Not connected
5
Connection established
0x23BA:001
(P580.01)
Modbus TCP statistics: Messages received
(MBTCP statistics: Rx messages)
–
Read only
 
–
From version 04.00
 
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
 
–
After the maximum value has been reached, the counter starts again "0".
 
0x23BA:002
(P580.02)
Modbus TCP statistics: Valid messages received
(MBTCP statistics: Valid Rx messag.)
–
Read only
 
–
From version 04.00
 
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x23BA:003
(P580.03)
Modbus TCP statistics: Messages with exceptions
(MBTCP statistics: Mess. w. except)
–
Read only
 
–
From version 04.00
 
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x23BA:005
(P580.05)
Modbus TCP statistics: Messages sent
(MBTCP statistics: Tx messages)
–
Read only
 
–
From version 04.00
 
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
 
0x23BE:001
(P585.01)
Modbus TCP/IP diagnostics of last Rx/Tx data: Receive offset
(MBTCP Tx/Rx diag: Rx offset)
0 ... [0] ... 240
–
From version 04.00
 
For diagnostic purposes, the last received message (max. 16 bytes) is displayed in 0x23BE:002 (P585.02). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x23BE:002
(P585.02)
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Rx message
(MBTCP Tx/Rx diag: Last Rx message)
–
Read only
 
–
From version 04.00
 
Display of the message received last.
0x23BE:003
(P585.03)
Modbus TCP/IP diagnostics of last Rx/Tx data: Transmit offset
(MBTCP Tx/Rx diag: Tx offset)
0 ... [0] ... 240
–
From version 04.00
 
For diagnostic purposes, the last sent message (max. 16 bytes) is displayed in 0x23BE:004 (P585.04). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x23BE:004
(P585.04)
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Tx message
(MBTCP Tx/Rx diag: Last Tx message)
–
Read only
 
–
From version 04.00
 
Display of the message sent last.