Status LEDs

Information on the CIP status can be obtained quickly via the "MS" and "NS" LED displays on the front of the inverter. In addition, the LEDs at the RJ45 sockets indicate the connection status.
 
The "MS" LED indicate the CIP module status.
LED "MS" (green/red)
CIP module status
Status/meaning
off
Nonexistent
The network option is not supplied with voltage.
On (green)
Operational
The network option works correctly.
Blinking green
Standby
The network option is not configured completely or the configuration is incorrect.
Blinking red
Major recoverable fault
The network option contains a correctable error.
on (red)
Major unrecoverable fault
The network option contains a non-correctable error.
Blinking green/red
Device self testing
The network option executes a self-test.
The "NS" LED indicate the CIP network status.
LED "NS" (green/red)
CIP network status
Status/meaning
off
No IP address
The network option is not supplied with voltage or has not received an IP address yet.
On (green)
Connected
The network option works correctly an has established a connection to the master.
Blinking green
No connections
The network option
–
works correctly,
 
–
has been assigned to an IP address,
 
–
has not been implemented into the network yet by the client.
 
Blinking red
Connection timeout
A time-out has occurred.
on (red)
Duplicate IP
The network option cannot access the network (IP address conflict).
Blinking green/red
Device self testing
The network option executes a self-test.
 
Status displays at the RJ45 sockets
The LEDs at the RJ45 sockets indicate the connection status to the network:
LED "Link" (green)
Status/meaning
off
No connection to the network.
on
A physical connection to the network is available.
LED "Activity" (yellow)
Status/meaning
off
No data transfer.
on or flickers
Data is exchanged via the network.