Information on the network

The following parameters show information on the network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2382:001
(P511.01)
Active PROFINET settings: IP address
(PROFINET diag.: IP address)
–
Read only
 
–
From version 02.00
 
Display of the active IP address.
0x2382:002
(P511.02)
Active PROFINET settings: Subnet
(PROFINET diag.: Subnet)
–
Read only
 
–
From version 02.00
 
Display of the active subnet mask.
0x2382:003
(P511.03)
Active PROFINET settings: Gateway
(PROFINET diag.: Gateway)
–
Read only
 
–
From version 02.00
 
Display of the gateway address.
0x2382:004
(P511.04)
Active PROFINET settings: Station name
(PROFINET diag.: Station name)
–
Read only
 
–
From version 02.00
 
Display of the active station name.
0x2382:005
(P511.05)
Active PROFINET settings: MAC Address
(PROFINET diag.: MAC Address)
–
Read only
 
–
From version 02.00
 
Display of the active MAC address.
0x2388
(P516.00)
PROFINET status
(PROFINET status)
–
Read only
 
–
From version 02.00
 
Bit coded display of the current Bus status.
Bit 0
Initialized
The network component is initialised.
Bit 1
Online
After initialisation, the network component waits for a communication partner and the system power-up.
Bit 2
Connected
The network component has established a cyclic I/O communication relationship to a communication partner.
Bit 3
IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
Bit 4
Hardware fault
Bit 6
Watchdog elapsed
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e.g. by cable break or failure of the IO Controller.
–
PROFINET communication changes to the "No_Data_Exchange" state.
 
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in 0x2859:001 (P515.01) is triggered in the inverter.
Bit 7
Protocol error
Bit 8
PROFINET stack ok
Bit 9
PROFINET stack not configured
Bit 10
Ethernet controller fault
Bit 11
UDP stack fault
0x2389:001
(P517.01)
PROFINET error: Error 1
(PROFINET error: Error 1)
–
Read only
 
–
From version 02.00
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:002 (P517.02).
 
0
No error
1
Reserved
2
Unit ID unknown
3
Max. units exceeded
4
Invalid size
5
Unit type unknown
6
Runtime plug error
7
Invalid argument
8
Service pending
9
Stack not ready
10
Command unknown
11
Invalid address descriptor
0x2389:002
(P517.02)
PROFINET error: Error 2
(PROFINET error: Error 2)
–
Read only
 
–
From version 02.00
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:001 (P517.01).
 
Bit 7
IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
Bit 8
Station name problem
The station name must be assigned according to the PROFINET specification.
Bit 9
DataExch left
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e. g. by cable break.
–
PROFINET communication changes to the "No_Data_Exchange" state.
 
–
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in 0x2859:001 (P515.01) is triggered in the device.
 
Bit 10
Stack boot error
Bit 11
Stack online error
Bit 12
Stack state error
Bit 13
Stack revision error
Bit 14
Initialization problem
The stack cannot be initiated with the user specifications. A reason might be, e. g., a station name that does not correspond to the PROFINET specification.
Bit 15
Stack init error