Status LEDs
Information on the CIP status can be obtained quickly via the
"MS" and "NS" LED displays on the front of the inverter. In addition, the LEDs at the RJ45 sockets indicate the connection status.
The "MS" LED indicate the CIP module status.
|
LED "MS" (green/red)
|
CIP module status
|
Status/meaning
|
|
off
|
Nonexistent
|
The network option is not supplied with voltage.
|
|
On (green)
|
Operational
|
The network option works correctly.
|
|
Blinking green
|
Standby
|
The network option is not configured completely or the configuration is incorrect.
|
|
Blinking red
|
Major recoverable fault
|
The network option contains a correctable error.
|
|
on (red)
|
Major unrecoverable fault
|
The network option contains a non-correctable error.
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
The "NS" LED indicate the CIP network status.
|
LED "NS" (green/red)
|
CIP network status
|
Status/meaning
|
|
off
|
No IP address
|
The network option is not supplied with voltage or has not received an IP address yet.
|
|
On (green)
|
Connected
|
The network option works correctly and has established a connection to the scanner.
|
|
Blinking green
|
No connections
|
The network option
–
works correctly,
–
has been assigned to an IP address,
–
has not been implemented into the network yet by the scanner.
|
|
Blinking red
|
Connection timeout
|
A time-out has occurred.
|
|
on (red)
|
Duplicate IP
|
The network option cannot access the network (IP address conflict).
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
Status displays at the RJ45 sockets
The LEDs at the RJ45 sockets indicate the connection status to the network:
|
LED "Link" (green)
|
Status/meaning
|
|
off
|
No connection to the network.
|
|
on
|
A physical connection to the network is available.
|
|
LED "Activity" (yellow)
|
Status/meaning
|
|
off
|
No data transfer.
|
|
on or flickers
|
Data is exchanged via the network.
|