Asynchronous motor (ASM): Identifying Lh saturation characteristic

In case of an asynchronous motor, the relationship between current and torque is basically determined by the saturation behaviour of the mutual inductance. If the achieved torque accuracy, especially in the field weakening range should not be sufficient, the accuracy can be increased by the individual identification of the saturation characteristic. This behaviour can be measured by the servo inverter.
 
Conditions for the execution
–
Before this commissioning function is executed, the inverter characteristic and the motor parameters must be identified Motor equivalent circuit diagram data. 
 
–
The motor may be stalled.
 
–
The inverter is error-free and in "Switched on" device state.
 
 
Response of the motor during "standstill" performance
 
How to identify the Lh saturation characteristic:
The identification of the Lh saturation characteristic can take up to 11 minutes.
 
1.
If the servo inverter enabled, disable it Disable operation. 
 
2.
Select the drive mode [10] in parameter 0x2825: Lh saturation characteristic identification
 
3.
Enable the inverter to start the process.
 
–
Check the progress in 0x2823:002.
 
–
Disabling the inverter serves to abort the started procedure any time if required. Already determined characteristic values are rejected in this case.
 
 
 
After successful completion...
...the inverter will be disabled automatically and the points of the determined Lh saturation characteristic are set in the parameters 0x2C07:001 ... 0x2C07:017.
–
Save the changed settings.
The »EASY Starter« serves to save the parameter settings of the servo inverter as parameter file (*.gdc).Saving the parameter settings 
 
–
The inverter disable set automatically by the procedure can be deactivated again via the CiA402 control word 0x6040 (setting = 7, 15).
 
 
In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time undervoltage), the procedure is terminated with inverter disable without the settings being changed.
 
Load standard Lh saturation characteristic
If an incorrect Lh saturation characteristic has been determined or none at all, it is possible to load a standard Lh characteristic.
 
How to load the standard Lh saturation characteristic:
1.
The start is made via the parameter 0x2822:021 = 1.
 
2.
For permanent storage: after the process has been completed, save the Lh saturation characteristic set in .
The »EASY Starter« serves to save the parameter settings of the inverter as parameter file (*.gdc). Saving the parameter settings
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2822:021
Axis commands: Load default Lh saturation characteristic
Parameters for interaction with engineering tools.
0
Off/Ready
1
On/Start
2
In progress
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2C07:001
Inductance grid points (y) Lh saturation characteristic: y1 = L01 (x = 0.00 %)
0 ... [118] ... 400 %
Saturation characteristic of the mutual inductance of an asynchronous machine as a function of the magnetising current.
0x2C07:002
Inductance grid points (y) Lh saturation characteristic: y2 = L02 (x = 6.25 %)
0 ... [118] ... 400 %
0x2C07:003
Inductance grid points (y) Lh saturation characteristic: y3 = L03 (x = 12.50 %)
0 ... [118] ... 400 %
0x2C07:004
Inductance grid points (y) Lh saturation characteristic: y4 = L04 (x = 18.75 %)
0 ... [117] ... 400 %
0x2C07:005
Inductance grid points (y) Lh saturation characteristic: y5 = L05 (x = 25.00 %)
0 ... [116] ... 400 %
0x2C07:006
Inductance grid points (y) Lh saturation characteristic: y6 = L06 (x = 31.25 %)
0 ... [114] ... 400 %
0x2C07:007
Inductance grid points (y) Lh saturation characteristic: y7 = L07 (x = 37.50 %)
0 ... [111] ... 400 %
0x2C07:008
Inductance grid points (y) Lh saturation characteristic: y8 = L08 (x = 43.75 %)
0 ... [107] ... 400 %
0x2C07:009
Inductance grid points (y) Lh saturation characteristic: y9 = L09 (x = 50.00 %)
0 ... [100] ... 400 %
0x2C07:010
Inductance grid points (y) Lh saturation characteristic: y10 = L10 (x = 56.25 %)
0 ... [93] ... 400 %
0x2C07:011
Inductance grid points (y) Lh saturation characteristic: y11 = L11 (x = 62.50 %)
0 ... [86] ... 400 %
0x2C07:012
Inductance grid points (y) Lh saturation characteristic: y12 = L12 (x = 68.75 %)
0 ... [78] ... 400 %
0x2C07:013
Inductance grid points (y) Lh saturation characteristic: y13 = L13 (x = 75.00 %)
0 ... [71] ... 400 %
0x2C07:014
Inductance grid points (y) Lh saturation characteristic: y14 = L14 (x = 81.25 %)
0 ... [64] ... 400 %
0x2C07:015
Inductance grid points (y) Lh saturation characteristic: y15 = L15 (x = 87.50 %)
0 ... [57] ... 400 %
0x2C07:016
Inductance grid points (y) Lh saturation characteristic: y16 = L16 (x = 93.75 %)
0 ... [50] ... 400 %
0x2C07:017
Inductance grid points (y) Lh saturation characteristic: y17 = L17 (x = 100.00 %)
0 ... [42] ... 400 %