Estimate optimum magnetising current

In case of the given Lh saturation behaviour, there is (usually) a magnetising current where the torque efficiency is highest. This magnetising current can be determined by the servo inverter.
–
Executing this function also compresses or extends the Lh saturation characteristic (interpolation points 0x2C07:001 ... 0x2C07:001).
 
–
After the function has been executed, the determined magnetising current is entered in 0x2C02:003.
 
 
Preconditions for the performance
–
Before this commissioning function is executed, the motor parameters and the Lh saturation characteristic must be identified Motor equivalent circuit diagram data. 
 
–
The motor must be stalled.
 
 
Response of the motor during "standstill" performance
 
How to estimate the optimal magnetising current:
1.
Start Axis commands: estimate optimum magnetising current parameter with = 1. 0x2822:023
 
2.
After the process has been completed, save the changed inverter parameters:
 
–
Lh saturation characteristic (0x2C07:001 ... 0x2C07:017)
 
–
Magnetising current0x2C02:003
The »EASY Starter« serves to save the parameter settings of the inverter as parameter file (*.gdc). Saving the parameter settings
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2822:023
Axis commands: Estimate optimum magnetizing current
Parameters for interaction with engineering tools.
0
Off/Ready
1
On/Start
2
In progress
3
Action cancelled
4
No access
5
No access (Device disabled)