Extended settings for identification

 
For determining the characteristic, the current controller is automatically parameterised at the start of the identification process. In case of motors with a very low stator leakage inductance (< 1 mH), the automatic parameterisation can fail and the actual identification process is aborted with an error message such as "short circuit".
 
–
For this case, it is possible to set the current controller manually via the
0x2942
parameter.
 
–
The 0x2DE0:001 parameter serves to select whether the current controller should be calculated automatically or the values in
0x2942
are effective.
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2DE0:001
Service settings: Current controller identification settings
Whether the current controller shall be adapted automatically for the identification or set manually, is selected via:
–
0x2942:001 (Gain)
 
–
0x2942:002 (Reset time)
 
0
Automatic
1
Manuell (0x2942)
0x2DE0:003
Service settings: Resolver - position detection dynamics
20 ... [100] ... 100 %
Setting of the dynamics for the resolver evaluation.
–
100% ≡ max. dynamics
 
–
<100% ≡ reduced dynamics
 
0x2DE0:004
Service settings: Resolver - 8 kHz safety signal
Usually ,the Der 8-kHz carrier frequency is only activated for the safety version. This parameter can also be used to switch it on and off.
0
Automatisch durch Gerätetyp
1
On
2
Aus
0x2DE0:007
Service settings: Use measured voltage
Activation of voltage measurement.
Only for devices for which voltage measurement is possible.
0
Aus
1
On