Compensating for inverter influence

Conditions for the execution
–
The motor may be stalled.
 
–
The inverter is switched on and error-free.
 
 
Response of the motor during performance
If the motor is not braked, the motor will move slightly
 
Disabling the inverter serves to abort the started procedure any time if required. Already determined characteristic values are rejected in this case.
 
How to detect the inverter characteristic:
1.
Disable the servo inverter.
 
2.
Change to the "inverter characteristic: identification" operating mode. 0x2825 = 8
 
3.
Enable the servo inverter.
 
The procedure starts.

After the successful completion, the inverter is automatically disabled and the points of the detected inverter characteristic are set in parameter 0x2947t.
1.
Save the changed settings.
 
2.
The inverter characteristic must only be detected again if the servo inverter, the motor or the motor cable have been replaced.
 
3.
The inverter disable set by the procedure can be deactivated via the control word. 0x6040 = 7
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2947:001
Inverter characteristic: Value y1
0.00 ... [0.00] ... 20.00 V
The inverter characteristic (consisting of 17 values) is calculated and set in the course of the automatic inverter characteristic identification.
Note!
Changing these values is not recommended by the manufacturer.
0x2947:002
Inverter characteristic: Value y2
0.00 ... [0.00] ... 20.00 V
0x2947:003
Inverter characteristic: Value y3
0.00 ... [0.00] ... 20.00 V
0x2947:004
Inverter characteristic: Value y4
0.00 ... [0.00] ... 20.00 V
0x2947:005
Inverter characteristic: Value y5
0.00 ... [0.00] ... 20.00 V
0x2947:006
Inverter characteristic: Value y6
0.00 ... [0.00] ... 20.00 V
0x2947:007
Inverter characteristic: Value y7
0.00 ... [0.00] ... 20.00 V
0x2947:008
Inverter characteristic: Value y8
0.00 ... [0.00] ... 20.00 V
0x2947:009
Inverter characteristic: Value y9
0.00 ... [0.00] ... 20.00 V
0x2947:010
Inverter characteristic: Value y10
0.00 ... [0.00] ... 20.00 V
0x2947:011
Inverter characteristic: Value y11
0.00 ... [0.00] ... 20.00 V
0x2947:012
Inverter characteristic: Value y12
0.00 ... [0.00] ... 20.00 V
0x2947:013
Inverter characteristic: Value y13
0.00 ... [0.00] ... 20.00 V
0x2947:014
Inverter characteristic: Value y14
0.00 ... [0.00] ... 20.00 V
0x2947:015
Inverter characteristic: Value y15
0.00 ... [0.00] ... 20.00 V
0x2947:016
Inverter characteristic: Value y16
0.00 ... [0.00] ... 20.00 V
0x2947:017
Inverter characteristic: Value y17
0.00 ... [0.00] ... 20.00 V
 
In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time undervoltage), the procedure is terminated with inverter disable without the settings being changed.