Basic setting

The following describes the steps required for configuring the speed control.
 
1.
0x6060Set the manufacturer spanning operating mode "CiA: Velocity mode (vl) [2]" or "CiA: Cyclic sync velocity mode (csv) [9]".
 
–
A detailed description of the "CiA: Velocity mode (vl)" operating mode can be found in the section Operating mode "CiA 402 velocity mode (vl)" .
 
–
A detailed description of the "CiA: Cyclic sync velocity mode (csv)" operating mode can be found in the section Operating mode "CiA 402 cyclic sync velocity mode (csv)" .
 
 
2.
Set the maximum motor speed in Max. motor speed. 0x6080
 
3.
Set the rated motor torque in Rated motor torque. 0x6076
 
4.
Set the positive torque limit. 0x60E0
 
5.
Set the negative torque limit. 0x60E1
 
 
The speed control is now active and the inverter responds to the speed setpoint.