Basic setting
1.
Set the manufacturer spanning operating mode "CiA: Cyclic sync torque mode (cst) [10]" according to CiA402.
–
A detailed description of this operating mode can be found in the "Operating mode "CiA 402 cyclic sync torque mode (cst)"" section.
2.
Set the rated motor torque.
0x6076
0x60763.
Set the permissible maximum torque.
0x6072
0x6072–
The maximum torque is preset in 0x6072.
–
The change of the positive and negative limit of the maximum torque is described in the "Torque limits" section.
4.
Parameterise speed limit. 0x2946
–
The maximum speed is preset.
0x6080
0x6080–
The change of the upper and lower speed limit is described in the "Speed limitation" section.
5.
Define a torque setpoint for the torque control instead of a speed setpoint. The value is given in percent and based on the rated motor torque set in 0x6076.
The torque control with speed limitation is now active and the inverter responds to the defined torque setpoint.