Pole position identification (PPI) with minimum movement

NOTICE
Mechanical damage of the motor caused by hanging loads!
Possible consequences: Irreversible damage of the motor.
▶
The motor must not be braked or blocked during the pole position identification. Thus, this function must not be used for hanging loads!
 
 
 
NOTICE
Thermal overload of the motor!
The motor may be permanently damaged.
▶
Before executing the pole position identification, check that the following monitoring systems are parameterised correctly in order to prevent a permanent damage of the motor in the event of an error:
 
▶
 
▶
 
 
 
Functional description
If servo control for synchronous motor is set and if no error is pending, the current position is memorised after controller enable, and the current is increased along a ramp for 10 s to 35 % of the rated motor current. This will cause the rotor to align, which, however, is compensated by a position control. If the rotor makes an electrical movement of more than 20°, an error message is output, and the value measured is discarded. This might occur in the case of motors with considerable detent torques.
If the current has reached its final value, a plausibility check is executed after a short interval: in order to detect a non-permissible blocking of the motor, a positive and a negative test angle (± 20°) relative to the current position are defined after the identification. The motor must align itself to these two test angles within a tolerance of 25 %.
 
Conditions for the execution
–
The motor must not be braked or blocked during the pole position identification.
 
–
The servo inverter is error-free and in Switched on device state.
 
 
Response of the motor during performance
The motion of the motor will maximally correspond to the set "Max. permissible motion" (Lenze setting: 20°). If a greater motion is detected via the encoder system, the pole position identification is cancelled and the parameterised error response (Lenze setting: Fault) is triggered.
 
How to execute the pole position identification PLI (min. movement):
1.
If the servo inverter is enabled, disable it.Enable operation
 
2.
Set the object 0x2825 to "6" to change to the "pole position identification PLI (min. movement)" operating mode.
 
3.
Enable the servo inverter to start the process.
Note: Inhibiting the controller serves to abort the started procedure any time if required without changing the settings.
 
 
After the pole position identification has been completed successfully...
...the controller is inhibited automatically and the pole position determined for the activated feedback system is set in the 0x2C03:002 object.
–
Save the changed settings.
The »EASY Starter« serves to save the parameter settings of the servo inverter as parameter file (*.gdc). This file can then be imported in the »PLC Designer«. Saving the parameter settings
 
–
The inverter disable set automatically by the procedure can be deactivated again via the CiA402 control word 0x6040. Enable operation
 
 
Adapt pole position identification PLI (min. movement)
The process of pole position identification described above can be adapted to the respective machine and the existing moments of inertia by using the parameters described in the following.
 
NOTICE
Thermal overload of the motor!
The motor may be permanently damaged.
▶
If no temperature monitoring is available in the motor, and/or the I²xt motor monitoring and the maximum current monitoring are not parameterised correctly, the motor can be permanently damaged if the current amplitude is set too high!
 
▶
 
▶
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C62:001
Pole position identification (min. movement) settings: Current amplitude
1 ... [25] ... 1000 %
–
Setting can only be changed if the inverter is disabled.
 
Percentage adaptation of the current amplitude.
–
For large machines, high mass inertia values or for linear direct drives, the current amplitude usually must be increased.
 
–
Default setting 25 % ≡ 35 % of Rated motor current (0x6075)
 
Note!
If the current amplitude is set to >  100  %, the device utilisation (Ixt) monitoring and/or one of the motor monitoring functions may respond and cause the abort of the pole position identification.
0x2C62:002
Pole position identification (min. movement) settings: Ramp time
1 ... [10] ... 600 s
–
Setting can only be changed if the inverter is disabled.
 
Percentage adaptation of the rate of current rise.
0x2C62:003
Pole position identification (min. movement) settings: Gain
0 ... [0] ... 1000 %
Adaptation of the proportional PI controller gain.
With the Lenze setting "0 %",the PI controller works as an I controller.
0x2C62:004
Pole position identification (min. movement) settings: Reset time
0.1 ... [62.5] ... 6000.0 ms
Adaptation of the reset time of the PI controller.
–
In order to be able to compensate a positional variation faster, first the reset time should be reduced. If this does not result in the desired behaviour, the proportional gain can be increased.
 
–
Ensure that the position control does not get unstable. We therefore recommend you to use an I controller.
 
0x2C62:005
Pole position identification (min. movement) settings: Max. move permitted
1 ... [20] ... 90 °
Adaptation of the permitted movement.
–
The pole position identification comprises a monitoring function for the follow-up control. If a movement greater than the permissible movement set is detected by the encoder system, the pole position identification is aborted and the error response parameterised is tripped:
 
–
In order to detect a non-permissible blocking of the machine, a positive and negative test angle relative to the current position are defined after the identification. The machine must align itself to these two test angles within a tolerance of 25 %. The size of the test angle corresponds to the max. move permitted set here.
 
0x2C62:006
Pole position identification (min. movement) settings: Absolute current amplitude
–
Read only: x.xx A
 
Display of the absolute current amplitude.