Pole position identification (PPI) without movement

The "Pole position identification (PLI) without movement" function can also be used if no motor revolution is possible (holding brake active).
 
NOTICE
With an incorrect parameter setting and dimensioning of the inverter, the maximum permissible motor current may be exceeded during the pole position identification.
Possible consequences: Irreversible damage of the motor
▶
Set the motor data correctly. Motor data 
 
▶
Only use an inverter that is performance-matched to the motor.
 
 
 
DANGER!
Uncontrolled acceleration of the motor!
Undefined state of the feedback system, caused by wire breakage!
▶
Each pole position identification causes an update of the pole position set in the device! Therefore, ensure that the response to open circuit in the feedback system is set to Lenze setting "1: Fault" in 0x2C45! Otherwise, the status of the feedback system in case of open circuit is undefined and the pole position can assume any value. There is a danger that the machine accelerates in an uncontrolled way after pole position identification!
 
 
 
NOTICE
Device state "switched-on"/"operation"
▶
The process of the pole position identification only lasts some milliseconds. During the pole position identification, the device status does not change. Only after the pole position identification, the Operation enabled device status changes to the Operation enabled device status.
 
▶
If pole position identification is started via parameter 0x2825, the inverter is automatically disabled at the end of the pole position identification process.
 
 
 
Conditions
–
The wiring of the three motor phases and the motor encoder must be carried out according to the specifications from the mounting instructions.
 
–
The inverter is ready for operation (no fault active).
 
–
For the pole position identification (PPI) without movement, the motor must be at standstill.
 
 
NOTICE
▶
During the pole position identification, the error 0xFF13 ("identification cancelled") may occur. This may be an indication that the motor features are not suitable for this PLI process.
 
 
 
Functional description
After inverter enable, a defined pulse pattern is output that provides currents up to approx. maximum motor current. The respective currents are measured. Based on these currents, the field distribution can be detected so that the pole position can be calculated. Then, the inverter is automatically disabled.
The pole position identification PLI (without movement) does not need any parameterisation.
 
Preconditions for the performance
–
The wiring of the three motor phases and the feedback must be carried out in accordance with the specifications from the hardware manual.
 
–
The motor may be stalled.
 
–
The servo inverter is error-free and in Switched on device state.
 
–
Please observe the notes in the Synchronous motor: Pole position identification (PPI)section.
 
 
Response of the motor during performance
The current test pulses cause audible engine noises that may be increased by the machine mechanics depending on the mechanical coupling!
 
How to execute the pole position identification PLI (without movement):
1.
If the servo inverter is enabled, disable it.Enable operation
 
2.
Set the object 0x2825 to "7" to change to the "pole position identification PLI (without movement)" operating mode.
 
3.
Enable the servo inverter to start the process.
Note: Inhibiting the controller serves to abort the started procedure any time if required without changing the settings.
 
 
After the pole position identification has been completed successfully...
...the controller is inhibited automatically and the pole position determined for the activated feedback system is set in the 0x2C03:002 object.
–
For permanent storage, the changed settings from the servo inverter must be uploaded in the Controller.
The »EASY Starter« serves to save the parameter settings of the servo inverter as parameter file (*.gdc). Saving the parameter settings
 
–
The inverter disable set automatically by the procedure can be deactivated again via the CiA402 control word 0x6040. Enable operation
 
 
Optional settings (starting performance)
Optionally, a pole position identification without motion can be activated after switching on the servo inverter.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C63:001
PPI without movement: Execution
–
Setting can only be changed if the inverter is disabled.
 
Start behavior (with or without pole position identification before the start).
0
Disabled
No pole position is identified.
1
Only after 1st enable/encoder error
After the first controller enable and after each encoder wire breakage, a PLI without movement takes place.
CAUTION!
After an encoder wire breakage, the drive may accelerate in an uncontrolled manner subsequent to the pole position identification.
–
Cause: In case of a wire breakage, the feedback system state is undefined and the pole position assumes any value.
 
–
Remedy: Set the error response "Trouble" (0x2C450x2C45 = 2) for an encoder wire breakage in order that the pole position will be identified after a wire breakage.
 
2
After each enable
After every inverter release, the pole position is identified without any movement.
0x2C63:002
PPI without movement: Current adjust factor
50 ... [100] ... 500 %
–
Setting can only be changed if the inverter is disabled.