SinCos absolute value encoder with HIPERFACE® protocol

The following SinCos encoder types with HIPERFACE
®
protocol are supported by the inverter:
Type
Increments/revolution
Absolute revolutions
Type code
AM1024-8V-H (SRM50)
1024
4096
(Multiturn)
39
AM1024-8V-H (SFM60)
1024
39
AM1024-8V-K2 (SRM50S)
1024
39
AM128-8V-H (SKM36)
128
55
AM16-8V-H (SEL37)
16
71
AM16-8V-H (SEL52)
16
71
AM512-8V-H (SCM70)
512
7
AS1024-8V-H (SRS50)
1024
4096
(Single-turn)
34
AS1024-8V-K2 (SRS50S)
1024
34
AS16-8V-H (SEK37)
16
66
AS16-8V-H (SEK52)
16
66
AS512-8V-H (SCS70)
512
2
 
Use of non-supported encoder types
If the type code of the encoder used is not listed in the table of supported encoder types, this encoder can be introduced to the inverter via the 0x2C41:002 and 0x2C41:003 parameters.
In this context, please also observe the information provided in the parameter description 0x2C41:008.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2822:026
Axis commands: Get motor encoder information (HIPERFACE®)
Command for reading out data from the connected motor encoder.
0
Off/Ready
1
On/Start
2
In progress
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2C41:001
Motor encoder settings (HIPERFACE®): Type code detected
–
Read only
 
Type code read out of the encoder.
This value is "0" if ...
–
a sin/cos encoder is set (0x2C40 = 2);
 
–
a communication error has occurred.
 
0x2C41:002
Motor encoder settings (HIPERFACE®): Type code manual input
0 ... [0] ... 255
–
Setting can only be changed if the inverter is disabled.
 
Manual setting of the encoder type code (display in 0x2C41:001).
0x2C41:003
Motor encoder settings (HIPERFACE®): Manual input - Number of detectable motor encoder revolutions
1 ... [1] ... 65535
–
Setting can only be changed if the inverter is disabled.
 
Manual setting of the number of distinguishable revolutions.
0x2C41:004
Motor encoder settings (HIPERFACE®): Error response
Selection of the response for communication errors or in the event of an unknown encoder.
0
No response
1
Fault > CiA402
2
Warning
0x2C41:005
Motor encoder settings (HIPERFACE®): Serial number
–
Read only
 
The displayed serial number can be used for identifying an encoder change.
0x2C41:006
Motor encoder settings (HIPERFACE®): Actual position (raw data)
–
Read only
 
The encoder-internal position value is output without being converted.
0x2C41:007
Motor encoder settings (HIPERFACE®): No. of periods detected
–
Read only
 
Display of the encoder increment according to encoder nameplate or type code.
0x2C41:008
Motor encoder settings (HIPERFACE®): Type code verification
–
Read only
 
If an encoder is connected that is not supported by the firmware, it will be displayed here.
In this case, the same response takes place as in case of a communication error. The error can be removed by manually setting the type code in 0x2C41:002. This serves to signalise to the firmware that the number of distinguishable revolutions is as well set correctly in 0x2C41:003 by the user.
0
Unknown - manual data input
If an encoder is connected that is not supported by the firmware, it will be displayed here.
1
Known - parameterisation ok
0x2C41:009
Motor encoder settings (HIPERFACE®): Encoder type
–
Read only
 
Display of the detected encoder type (rotary/linear).
0
Rotative encoder
1
Linear encoder
0x2C41:010
Motor encoder settings (HIPERFACE®): Period length of linear encoder
–
Read only: x nm
 
Display of the period length of the linear encoder.