Evaluation of the signal quality

Signal quality
The signal quality is evaluated by the 0x2C42:004 parameter, which is used to monitor the initial read-out and setting of the position.
If a transmission error should occur:
–
The current angular drift is marked as invalid in parameter 0x2833, bit 7
 
–
The inverter maintains its operating status
 
 
Angular drift
Communication with the encoder is no longer monitored during angular drift determination.
 
 
The value displayed in 0x2C42:003 is determined in different ways depending on the type of encoder:
–
Determination of the current angular drift for the SinCos encoder
In the case of an incremental SinCos encoder, the pulses between two zero pulse events of the Z-track are counted. Assuming that there are no faults, this value corresponds to the set number of increments. The accuracy of this process corresponds to ± 1 increment graduation of the encoder, with the difference between the set number of increments and the counted pulses being converted to an angle with an accuracy of ±0.1°. The disadvantage is that an updated angular drift value only become available at the end of a complete encoder revolution. In turn, this means that the update rate depends on the speed.
 
 
–
Determination of the current angular drift for the SinCos Hiperface® absolute value encoder
In the case of a SinCos absolute value encoder with HIPERFACE® protocol, no Z-track is available; instead, the position is regularly read out of the encoder. When the first encoder read-out operation is performed (after power-up or elimination of wire breakage), the encoder position is used to initialise the internal device counter unit and to set an internal device position. All other read-out processes from the encoder are used to generate a difference between the internal device position and the encoder position. Assuming that there are no faults, the difference is zero. However, the dead time of the communication with the encoder means that the accuracy of the process is dependent on the speed and therefore restricted compared to the zero pulse process. However, the advantage is that the update rate does not depend on the speed, but is instead only determined by the communication rate. The update rate is encoder-specific and is generally in the range between 30 ... 50 ms.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C42:003
Encoder settings: Angle drift
–
Read only: x.x °
 
Display of the angular drift of the current angle error.
This indicates whether too many or two few pulses have been detected by the internal device counter unit for EMC-related reasons.
0x2C42:004
Encoder settings: Actual amplitude signal quality
–
Read only: x %
 
The signal quality indicates the actual amplitude of the SinCos analog signals with regard to 1 Vss = 100 %.
–
The signal quality should be between 95 ... 105 %.
 
–
There is no need for optimisation if the signal quality is within the tolerance zone for the analog encoder signals given in the data sheet of the encoder manufacturer.
 
0x2C42:008
Encoder settings: Encoder voltage cos track
–
Read only: x.xxx V
 
0x2C42:009
Encoder settings: Encoder voltage sin track
–
Read only: x.xxx V
 
0x2C42:010
Encoder settings: TTL/HTL signal evaluation
–
Setting can only be changed if the inverter is disabled.
 
1
High resolution encoder - 4-fold evaluation
4
Low resolution encoder
5
Count input - A=positive/B=negative
6
Count input - A=increments/B=sign