Notch filter (band-stop filter)
Due to the high dynamic performance or limit frequency of the closed current control loop, mechanical natural frequencies can be activated which may lead to an unstable speed control loop in the case of resonance.
To mask out or at least damp these resonant frequencies, two notch filters are integrated in the speed control loop of the inverter. In the Lenze setting, these filters are switched off:
Use of the notch filters depending on the resonant frequency
WARNING!Improperly set notch filters have a negative impact on the response and disturbance behaviour of the speed control: increased overshoot of the motor speed in case of response behaviour and / or higher speed deviations (extreme case: complete instability of the drive)
In the case of impairment,
▶
the drive that is still running must either be coasted down by activating the inverter disable or immediately be brought to a standstill via a brake.
▶
the speed controller must be optimised again afterwards.
▶
the test procedure must be repeated.
|
Output frequency
|
Use of notch filters
|
|
0...1/2 flimit_speed_controller
|
No
|
|
1/2 flimit_speed_controller...f_limit_speed-Controller
|
yes, with restriction
|
|
<flimit_speed_controller
|
yes, without restriction
|
–
The notch filters are suitable for use with resonant frequencies equal to or higher than the limit frequency of the speed controller:
–
Resonant frequencies
≥
flimit_speed_controller = 70 Hz ... 110 Hz–
For resonant frequencies lower than the limit frequency of the speed controller, the use of suitable speed profiles with an S-shaped ramp is recommended.
Setting the notch filters
Since the exact frequency response of the speed control path in most cases is not known beforehand, an experimental procedure for setting the notch filters is described in the following.
How to set the notch filters:
1.
Set and optimise current controller, see section Current controller .
2.
Adapt the speed controller reset time to the filter time constant of the actual speed filter time and the equivalent time constant of the current control loop:
Note: The setting of the reset time includes the equivalent time constant of the current control loop. The 500 μs indicated are typical in a power range of up to 50 kW. Above this value, greater time constants may occur.
3.
Slowly increase the proportional gain of the speed controller in 0x2900:001 until the speed control loop starts to be unstable (acoustic determination, measurement of the motor current or recording of the speed output signal).
4.
Measure the oscillation frequency using an oscilloscope:
5.
Set the oscillation frequency determined as filter frequency in 0x2944:001.
6.
Set the filter width to 40 % of the filter frequency in 0x2944:002.
7.
Se the filter depth to 40 dB in 0x2944:003.
–
If "0 dB" is set (default setting), the filter is not effective.
8.
Further increase the proportional gain of the speed controller in 0x2900:001 until the speed control loop starts to be unstable again.
–
If the oscillation frequency has changed now, readjust the filter frequency by trimming. The use of a second filter is ineffective here.
–
If the oscillation frequency remains the same, readjust the filter depth and/or the filter width by trimming (the first reduces the amplitude, the second lets the phase rotate faster).
–
Repeat step 8 until the desired behaviour or the limit of a sensible speed controller gain has been reached.
9.
Check the drive behaviour in case of quick stop (QSP)
–
Accelerate drive
–
Then, brake with quick stop (QSP) and check whether a reduced drive dynamics can be detected.
–
If so, reduce the influence of the filters until the reachable dynamics corresponds to the requirements.
NOTICE
▶
Readjust the speed controller after setting the notch filters (see section "Speed controller").
▶
Save the changed settings.
▶
The »EASY Starter« serves to save the parameter settings of the servo inverter as parameter file (*.gdc), see section Saving the parameter settings .
Parameter