Current controller
The current controller consists of a direct-axis current controller and a cross current controller which are both parameterised identically. The direct-axis current controller controls the field-producing current (D current). The cross current controller controls the torque-producing current (Q current).
Description of the function
The function controls the control cycle. The following model parameters are improved.
–
Inductance of the saturation characteristic
–
Setpoint step-change in the small signal behavior
This correspond to the maximum possible dynamics of the current controller and increases the stability limit of the higher-level control loops. The higher-level control loops are the position control and the speed control. The setpoint step-changes are compensated within half a PWM cycle.
Fig. 1: Characteristic with and without torque control
Activation of the function
In case of synchronous machines, this parameter is set by default to Enable [1] and in case of asynchronous machines to Disable [0].
How to activate the function
1.
Set parameter to [2].
The function is activated.
For a servo control, the current controller should always be optimized if a motor of another manufacturer with unknown motor data is used! For a V/f characteristic control, the current controller only has to be optimized if voltage vector controlActivate voltage vector control (Imin controller) is used, or if the motor functions “DC braking” or “flying restart process” are activated.
Automatically calculated settings for the current controller
If one of the values calculated exceeds the upper object limit, the value is limited to the limit value.
There is a coupling between the two control loops (direct-axis current controller, cross current controller) which makes every actuation of a controller occur as fault in the control loop of the other controller. This coupling can be compensated by activating the current controller feedforward control via object 0x2941.
For the automatic calculation of the two controller parameters (gain and reset time), the "Calc. current contr. param."function is provided via object 0x2822:013. The calculation function is based on the stator resistance 0x2C01:002 and the stator leakage inductance 0x2C01:003. Thus, these motor parameters must be parameterized before, e. g. by the manual entry of data sheet values. The calculated controller parameters can be optimized by means of an experimental adjustment subsequently. The procedure is described in sectionManual "current pulse" test mode
Equations for calculating the gain and reset time of the synchronous motor
|
Gain
|
Reset time
|
|
|
|
|
Parameter
|
Symbol
|
Description
|
Dimension unit
|
|
Vp
|
Current controller gain
|
V/A
|
|
|
Lss
|
Stator leakage inductance
|
H
|
|
|
-
|
TDead time
|
Equivalent time constant for the analog detection and scanning = 0.0002016 s
|
s
|
|
Tn
|
Current controller reset time
|
s
|
|
|
Rs
|
Stator resistance (value at 20° C)
|
Ω
|
Equations for calculating the gain and reset time of the asynchronous motor
|
Gain
|
Reset time
|
|
|
|
|
Parameter
|
Symbol
|
Description
|
Dimension unit
|
|
Vp
|
Current controller gain
|
V/A
|
|
|
-
|
σ
|
Leakage
|
|
|
-
|
Ls
|
Motor stator inductance
|
H
|
|
Lss
|
Motor stator leakage inductance
|
H
|
|
|
-
|
TDead time
|
Equivalent time constant for the analog detection and scanning = 0.0002016 s
|
s
|
|
Tn
|
Current controller reset time
|
s
|
|
|
Rs
|
Motor stator resistance (value at 20° C)
|
Ω
|
Debugging
The function depends on the saturation characteristic of the inductances in parameter 0x2c04 0x2c04.
For Lenze motors, this characteristic can be found in the motor table. In case of MCS motors, the characteristic values in the first 2 entries are too high. If there are any problems regarding the torque control, reduce these values. Lenze motors with the standard setting achieve a considerable higher performance.
In the following parameter, debugging is possible with the commissioning function Man. Test mode curr. Imp.. 0x2825
0x2825
0x2825 This function is documented. Here, the transient response of the current controller can be evaluated which shall considerably improve when the torque control is activated.
The following chart shows the this behavior.
–
Red characteristic without torque controller
–
Yellow characteristic with activated torque controller
If the course is worse with an activated torque control, the parameters of the inductance and saturation profile are faulty.
Parameter
Example
Applications with torque control with a switching frequency of 4 kHz reach the same dynamics as applications with 16 kHz without torque control. The stability limit of the speed controller increases depending on the switching frequency and filter setting by up to 100 %. Typical values are in the range of 30 % - 50 %. In case of applications that have already been solved with the previously found settings, an activation is not necessary.