ASM field controller
For motors with great rotor time constants or small rotor resistances, very high gain factors are calculated. Since the setting range of the field controller is limited to the double rated magnetising current, the field control loop in the case of these motors tends to a two-point response when the values calculated are entered.
The automatic calculation is made via the parameter 0x2822:016 = 1.
Starting from a calculated gain factor of approx. 1000 A/Vs, do not set the full value anymore.
Example
Calculated value: 10000 A/Vs
Setting: 3000 A/Vs
Calculation of the gain
Calculation of the reset time
|
Parameter
|
Symbol
|
Description
|
Dimension unit
|
|
Vp
|
Field controller gain
|
A/Vs
|
|
|
Tn
|
Field controller reset time
|
s
|
|
|
Lh
|
Mutual motor inductance (ASM)
|
H
|
|
|
Rr
|
Motor rotor resistance (ASM)
|
Ω
|
|
|
-
|
Tcurrent controller
|
Equivalent time constant of the current control loop = 0.0005 s
|
|
|
-
|
Tr
|
Motor rotor time constant
|
|
|
-
|
KPath
|
Gain of the control path
|
|
|
-
|
Lr
|
Motor rotor resistance (ASM)
|
H
|
Parameter