PSM operation outside the voltage range

The inverter control enables a synchronous motor to be operated outside the voltage range. If a motor is selected in the »EASY Starter«, the control is parameterised automatically.
Improve the transition from the base speed range to field weakening by activating the current controller: feedforward control parameter. 0x2941
–
The current controller precontrol is defined via the following parameters:
 
–
Motor parameter: stator resistance 0x2C01:002
 
–
Motor parameter: stator leakage inductance 0x2C01:003
 
–
Motor parameter (PSM): back EMF constant 0x2C03:001
 
 
–
If you want to operate a third-party motor in the field weakening range, you have to determine the parameters previously mentioned
 
Operation of synchronous motors outside the voltage range:
If pulse inhibit is set in the inverter, e.g. in case of an inverter disable or an error, the DC bus is loaded in accordance with the current speed (see equation).
• At high speed and outside the voltage range, the terminal voltage can be higher than the mains voltage!
• In order to prevent the DC bus from being loaded impermissibly high, connect a brake chopper to the DC bus!
 
The terminal voltage corresponds to the following equation
VK
Terminal voltage
n
Speed
Vrated
Rated mains voltage
nm
Rated motor voltage
–
Mains settings: rated mains voltage 0x2540:001
 
–
Motor parameter: rated speed 0x2C01:004
 
 
Delaying the buildup of field weakening
With the default setting (5 %), field weakening is initiated, thus ensuring that a punctual buildup of the field weakening current shortly before the voltage threshold is reached.
In the case of synchronous motors, setting the Voltage reserve range parameter may bring about a delayed start of field weakening for synchronous machines, e.g in order to slightly reduce the thermal load of the motor. 0x29E4