Correction of the stator leakage inductance (Lss)...
...and the current controller parameters by means of the saturation characteristic
For the most part, the electrical characteristics of the motor are the relevant factors for an optimal current controller setting (Vp, Ti), especially the stator resistance and the stator leakage inductance (Lss). However, modern motors have their stator leakage inductance changed along with the current level so that it is impossible to have an optimal current controller setting for all working points at all times.
For applications with operating phases that involve very different current and torque requirements and, at the same time, high requirements on dynamic drive behaviour, the i700 servo inverter provides the possibility of the correction of the stator leakage inductance and the current controller settings by means of the adjustable saturation characteristic.
The saturation characteristic is a typical characteristic of motors of one type/size. It does not depend on the maximum process current of the motor in the prevailing application. Thus the defined values should be based on the key data of the motors. These are rated motor current, peak motor current for a limited time and the ultimate motor current.
NOTICE
Impact of the saturation characteristic on the current controller feedforward control
▶
The saturation characteristic is not only used to correct the current controller, but it also influences the current controller feedforward control (can be activated via parameter 0x2941).
The following picture shows a typical saturation characteristic of an MCS motor:
The saturation characteristic represents the change in inductance (L/Ln) as a function of the motor current (I/Imax). The variables of both axes which were scaled to a reference value are represented as percentages.
–
When a Lenze motor is selected, the saturation characteristic is already filled with values typical of the series.
Distribution of the grid points
–
The saturation characteristic is represented by 17 grid points.
–
The 17 grid points are spaced on the X axis at equal intervals (equidistantly) in a range of 0 ... 100 %. The 100% value of the X axis refers to the current value (max. motor current in the process) set in parameter 0x2C05.
–
The y values for the grid points can be accessed via the subindices of parameter .
–
The 100 % value of a grid point refers to
–
the set motor stator leakage inductance 0x2C01:003 and
–
the set current controller gain Vp 0x2942:001.
–
Preferably select a display area of the grid points which includes at least the ultimate motor current. The current controller step response is then recorded actively only until the grid point with peak motor current. In order to prevent the motor winding from being overloaded, use the manual test mode "current pulse" for recording:
Manual "current pulse" test mode.
Manual "current pulse" test mode. –
The grid points with current setpoints above the peak motor current are determined through interpolation.
–
When the saturation characteristics for motor types are determined, it makes sense in some cases to select a scaled representation of the grid point distribution. This requires to know the highest value of the quotient from "ultimate motor current / rated motor current" of the motor series.
Example of determining the saturation characteristic
Given values:
–
Rated motor current: 5 A
–
Maximum motor current: 20 A
–
Maximum process current: 15 A
Proceeding
1.
Deactivate correction: Set all subindices (0x2C04:001 ... 0x2C04:017) to 100 %.
2.
Use 0x2C05 to set the maximum current up to which the motor is to be operated in the process (in this example "15 A").
3.
Adjust the current controller with different current setpoints by means of the manual test mode Manual "current pulse" test mode and take down the corresponding settings for Vp and Tn.
–
The procedure is described in section Manual "current pulse" test mode.
–
The current setpoints to be set for the corresponding adjustment in object 0x2835:001 result from the scaling of the maximum process current to the X axis of the saturation characteristic.
–
The grid points which are required to define the saturation characteristic with a sufficient quality varies from motor to motor and thus has to be determined individually.
–
For this example, currents that are part of the grid points 5, 9, 13, and 15 have been selected, and a measurement at rated motor current was carried out additionally:
See table "Specifications for adjustment / measured values" after this listing
4.
Create a characteristic based on the detected values for Vp (but do not enter any values in yet).
–
Determine the values of the grid points that have not been adjusted by interpolation between two values.
–
Note: This example assumes that the inductance does not change considerably below 3.75 A. For this reason, the same Vp value that resulted from the measurement with a motor current of 3.75 A was used for all grid points below 3.75 A.
5.
Set gain Vp and reset time Tn to the values that were determined during the adjustment with the rated motor current (in this example "5 A"):
6.
Scale Vp values on the Y axis of the characteristic to the Vp setting "3.8 V/A":
7.
Enter the percentage Vp values of the grid points into the subindices (0x2C04:001 ... 0x2C04:017):
See table "Setting of grid point 1 ... 17 in [%]" after this listing
8.
Enter the maximum process current ("15 A") in 0x6073 as the maximum current.
–
The settings made should now cause the same basic current characteristic irrespective of the current level.
–
Now that the current controller gain is actively corrected, the step responses may slightly differ from the previous measurements. In this case, the current controller parameters must be post-optimised for the last time.
9.
For permanent storage: save the characteristic determined.
The »EASY Starter« serves to save the parameter settings of the inverter as parameter file (*.gdc). Saving the parameter settings
The »EASY Starter« serves to save the parameter settings of the inverter as parameter file (*.gdc). Saving the parameter settings
|
Specifications for adjustment
|
Measured values
|
|||
|
Grid point
|
Scaling
|
Current setpoint
|
Vp [V/A]
|
Tn [ms]
|
|
5
|
0.25 * 15 A =
|
3.75 A
|
5.2
|
6.5
|
|
9
|
0.5 * 15 A =
|
7.5 A
|
2.6
|
4
|
|
13
|
0.75 * 15 A =
|
11.25 A
|
1.4
|
2.5
|
|
15
|
0.875 * 15 A =
|
12.38 A
|
1.0
|
2
|
|
17
|
1.0 * 15 A =
|
15 A
|
0.7
|
1.7
|
|
Rated motor current=
|
5 A
|
3.8
|
5
|
|
|
Setting of grid point 1 ... 17 in [%]
|
||||||||||||||||
|
y1
|
y2
|
y3
|
y4
|
y5
|
y6
|
y7
|
y8
|
y9
|
y10
|
y11
|
y12
|
y13
|
y14
|
y15y
|
y16
|
y17
|
|
137
|
137
|
137
|
137
|
137
|
109
|
92
|
80
|
68
|
61
|
53
|
45
|
37
|
32
|
26
|
22
|
19
|
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2C04:001
|
d-axis Lss saturation characteristic: y1 = L01 (x = 0.00 %)
0 ... [165] ... 400 %
|
Saturation characteristic of the leakage inductance.
The linear distribution via the current results from the maximum motor current (0x2C05).
|
|
|
0x2C04:002
|
d-axis Lss saturation characteristic: y2 = L02 (x = 6.25 %)
0 ... [200] ... 400 %
|
||
|
0x2C04:003
|
d-axis Lss saturation characteristic: y3 = L03 (x = 12.50 %)
0 ... [146] ... 400 %
|
||
|
0x2C04:004
|
d-axis Lss saturation characteristic: y4 = L04 (x = 18.75 %)
0 ... [117] ... 400 %
|
||
|
0x2C04:005
|
d-axis Lss saturation characteristic: y5 = L05 (x = 25.00 %)
0 ... [97] ... 400 %
|
||
|
0x2C04:006
|
d-axis Lss saturation characteristic: y6 = L06 (x = 31.25 %)
0 ... [82] ... 400 %
|
||
|
0x2C04:007
|
d-axis Lss saturation characteristic: y7 = L07 (x = 37.50 %)
0 ... [71] ... 400 %
|
||
|
0x2C04:008
|
d-axis Lss saturation characteristic: y8 = L08 (x = 42.75 %)
0 ... [62] ... 400 %
|
||
|
0x2C04:009
|
d-axis Lss saturation characteristic: y9 = L09 (x = 50.00 %)
0 ... [55] ... 400 %
|
||
|
0x2C04:010
|
d-axis Lss saturation characteristic: y10 = L10 (x = 56.25 %)
0 ... [50] ... 400 %
|
||
|
0x2C04:011
|
d-axis Lss saturation characteristic: y11 = L11 (x = 62.50 %)
0 ... [46] ... 400 %
|
||
|
0x2C04:012
|
d-axis Lss saturation characteristic: y12 = L12 (x = 68.75 %)
0 ... [43] ... 400 %
|
||
|
0x2C04:013
|
d-axis Lss saturation characteristic: y13 = L13 (x = 75.00 %)
0 ... [42] ... 400 %
|
||
|
0x2C04:014
|
d-axis Lss saturation characteristic: y14 = L14 (x = 81.25 %)
0 ... [41] ... 400 %
|
||
|
0x2C04:015
|
d-axis Lss saturation characteristic: y15 = L15 (x = 87.50 %)
0 ... [41] ... 400 %
|
||
|
0x2C04:016
|
d-axis Lss saturation characteristic: y16 = L16 (x = 93.25 %)
0 ... [41] ... 400 %
|
||
|
0x2C04:017
|
d-axis Lss saturation characteristic: y17 = L17 (x = 100.00 %)
0 ... [41] ... 400 %
|
||
|
0x2C04:018
|
d-axis Lss saturation characteristic: Activation Lss saturation characteristic
|
Switch on/off the correction by means of saturation characteristic.
|
|
|
0
|
Adjustment off
|
||
|
1
|
Adjustment on
|
||
|
0x2C05
|
Reference for current grid points (x) Lss saturation characteristic
0.0 ... [5.4] ... 2500.0 A
|
Setting of the maximum motor current.
Serves as reference value for the scaled current data of the X axis of the saturation characteristic.
|
|