PROFIsafe connection

PROFIsafe is the certified safety protocol for the transmission of safety-related data via PROFINET
®
.
 
The function supports the transfer of secure information via the PROFIsafe protocol according to the specification "PROFIsafe Profile for Safety Technology", Version 2.0, of the PROFIBUS user organization (PNO). The inverter forwards the PROFIsafe information to the function for secure evaluation.
 
Addressing
In order to ensure that a data telegram reaches the right node, a unique PROFIsafe destination address is necessary. If PROFIsafe has been chosen as the safety bus, the safety address will be used as the PROFIsafe destination address. This address must match the corresponding configuration of the safety PLC.
 
PROFIsafe Frame
The PROFIsafe data is transmitted in the second slot of a PROFINET data telegram. This must be taken into account during the hardware configuration of the safety PLC.
 
PROFINET data telegram
Header
Slot 1
Slot 2
Trailer
Data
PROFIsafe data
 
PROFIsafe data
In the PROFIsafe data, a bit is used to control a safety function.
The structure of the PROFIsafe data is described in the PROFIsafe profile. The length of the PROFIsafe data (or PROFIsafe message) is 16 bytes.
PROFIsafe message V2 mode
Bit offset
Byte offset
7
6
5
4
3
2
1
0
0...11
PROFIsafe process data
(PROFIsafe output data/PROFIsafe input data)
12
Control byte or status byte
13...15
CRC2
Signature from PROFIsafe process data, the PROFIsafe parameters and the running numbers.
The meaning of the PROFIsafe process data is described separately in the following chapters according to PROFIsafe output data and PROFIsafe input data.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x212A:002
S-Bus: PROFIsafe status
–
Read only
 
0
Init
1
Param
2
Data_Exchange
3
Data_Exchange_Passivated
4
Data_Exchange_Fault
5
Hardware_Failure
0x212A:003
S-Bus: PROFIsafe status byte
–
Read only
 
Bit  0
iPar_OK
Bit  1
Device_Fault/ChF_Ack_Req
Bit  2
CE_CRC
Bit  3
WD_timeout
Bit  4
FV_activated
Bit  5
Toggle_d
Bit  6
cons_nr_R
0x212A:004
S-Bus: PROFIsafe control byte
–
Read only
 
Bit  0
iPar_EN
Bit  1
OA_Req
Bit  2
R_cons_nr
Bit  3
Use_TO2
Bit  4
activate_FV
Bit  5
Toggle_h
Bit  6
ChF_Ack
Bit  7
Loopcheck