FSoE connection

Fail-safe-over-EtherCAT (FSoE) enables the transmission of safe information via FSoE protocol according to ETG.5100 S specification, version 1.2.0 of the EtherCAT user organisation (ETG).
Safety over EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
 
FSoE availability
i950 extended safety
Technology application
FSoE via onboard EtherCAT
FSoE via EtherCAT module I9MAFT0000000S
From safety firmware V1.1 with parameter set version V1.1
From safety firmware V1.2 with parameter set version V1.2
With Lenze components
With Beckhoff components
With Lenze components
With Beckhoff components
EtherCAT master
Lenze Controller
Beckhoff PLC
Lenze Controller
Beckhoff PLC
FSoE master
Lenze c250-S
TwinSAFE
Lenze c250-S
TwinSAFE
Device profile CiA 402
(0x4000 = 0)
From device firmware V01.04.01
Without SD card
-
-
CiA 402 Advanced
(0x4000 = 1)
From device firmware V01.04.01
With SD card
From device firmware V01.03.07
With SD card
-
All other technology applications
(0x4000 > 1)
From device firmware V01.04.01
With SD card
 
 
Addressing
A definite FsoE address ensures that a data frame reaches the correct node. If "FSoE" has been selected as safety bus, the safety address is at the same time accepted as the FSoE target address. This address must match the corresponding configuration of the safety PLC.
 
The checksums (CRC) of a parameter set are calculated via the set safety parameters. The calculated checksums of the safety parameter set must match the corresponding configuration of the safety PLC.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x212A:001
S-Bus: FSoE project CRC
0 ... [ ] ... 4294967295
–
Safety parameter (+Safety parameter list+)
 
0xE600:001
FSoE Slave Frame Elements: Command
–
Read only
 
0xE600:002
FSoE Slave Frame Elements: Connection ID
–
Read only
 
0xE600:003
FSoE Slave Frame Elements: CRC_0
–
Read only
 
0xE600:004
FSoE Slave Frame Elements: CRC_1
–
Read only
 
0xE600:005
FSoE Slave Frame Elements: CRC_2
–
Read only
 
0xE600:006
FSoE Slave Frame Elements: CRC_3
–
Read only
 
0xE600:007
FSoE Slave Frame Elements: CRC_4
–
Read only
 
0xE600:008
FSoE Slave Frame Elements: CRC_5
–
Read only
 
0xE600:009
FSoE Slave Frame Elements: CRC_6
–
Read only
 
0xE700:001
FSoE Master Frame Elements: Command
–
Read only
 
0xE700:002
FSoE Master Frame Elements: Connection ID
–
Read only
 
0xE700:003
FSoE Master Frame Elements: CRC_0
–
Read only
 
0xE700:004
FSoE Master Frame Elements: CRC_1
–
Read only
 
0xE901:001
FSoE Connection Communication Parameter: Version
–
Read only
 
0xE901:002
FSoE Connection Communication Parameter: Safety address
–
Read only
 
0xE901:003
FSoE Connection Communication Parameter: Connection ID
–
Read only
 
0xE901:004
FSoE Connection Communication Parameter: Watchdog Time
–
Read only
 
0xE901:006
FSoE Connection Communication Parameter: Connection Type
–
Read only
 
0
Master
1
Slave
0xE901:007
FSoE Connection Communication Parameter: Communication Parameter Length
–
Read only
 
0xE901:008
FSoE Connection Communication Parameter: Application Parameter Length
–
Read only
 
0xEA00:001
FSoE Connection Diagnosis: Connection State
–
Read only
 
0
Reset
1
Session
2
Connection
3
Parameter
4
Data
5
Failsafe