Supported commands
The following PROFIenergy commands are supported:
|
Command
|
Description
|
|
Start_Pause
|
Starts the energy saving function.
|
|
End_Pause
|
Stops the energy saving function.
|
|
Query_Mode
|
Requests the list of all supported energy modes.
|
|
Get_Mode
|
Requests the data of an energy mode.
|
|
PEM_Status
|
Requests the current status.
|
|
PEM_Status_with_CTTO
|
Requests the current status of dynamic values.
|
|
PE_Identify
|
Requests basic information on the modes.
|
|
Query_Version
|
Requests the versioning of the query.
|
|
Get_Measurement_List
|
Requests the list of the supported measured values.
|
|
Get_Measurement_List_with_object_number
|
Requests the list of supported measured values indicating the corresponding parameters.
|
|
Get_Measurement_Values
|
Requests the values of the measured values.
|
|
Get_Measurement_Values_with_object_number
|
Requests the values of the measured values indicating the corresponding parameters.
|
|
PE_Mode_ID
|
Manufacturer-specific energy saving mode
The energy saving mode is only active if the power section is inhibited. (0x2590:003, bit 0 = 1)
|