Safety-related characteristics Extended Safety
|
Basics of the safety-related characteristics
|
||||
|
|
|
Source of failure rates
|
SN 29500
|
When no values from the component manufacturers were available.
|
|
|
Average max. ambient temperature
|
60 °C
|
|
|
|
All safety functions except Safe Brake Control (SBC) for drive systems with motors with resolvers and SinCos encoders
|
||||
|
|
EN IEC 61508, Teil 1-7
EN 62061 |
Safety Integrity Level
|
SIL 3
|
|
|
PFH [1/h]
|
< 1 E-09
|
< 1 % of SIL 3
|
||
|
PFDavg (T)
|
< 1 E-04
|
< 10 % of SIL 3 after T = 20 years
|
||
|
SFF
|
99%
|
|
||
|
Proof test interval T
|
20 years
|
Mission time
|
||
|
EN ISO 13849-1
|
Performance Level
|
e
|
|
|
|
Category
|
4
|
|||
|
MTTFavg
|
High
|
> 250 years
|
||
|
|
Mean diagnostic coverage DCavg
|
95%
|
||
|
All safety functions except Safe Brake Control (SBC) for drive systems with motors with HIPERFACE DSL® encoders (OCT)
|
||||
|
|
EN IEC 61508, Teil 1-7
EN 62061 |
Safety Integrity Level
|
SIL 2
|
|
|
PFH [1/h]
|
< 5 E-09
|
< 0.5 % of SIL 2
|
||
|
PFDavg (T)
|
< 5 E-04
|
< 5 % of SIL 2 after T = 20 years
|
||
|
SFF
|
> 90 %
|
|
||
|
Proof test interval T
|
20 years
|
Mission time
|
||
|
EN ISO 13849-1
|
Performance Level
|
d
|
|
|
|
Category
|
3
|
|||
|
MTTFavg
|
High
|
> 300 years
|
||
|
|
Mean diagnostic coverage DCavg
|
Medium
|
> 90 %
|
|
|
Safe Brake Control (SBC) safety function independent of the parameterized motor encoder system
|
||||
|
|
EN IEC 61508, Teil 1-7
EN 62061 |
Safety Integrity Level
|
SIL 2
|
|
|
PFH [1/h]
|
< 1 E-08
|
< 1 % of SIL 2
|
||
|
PFDavg (T)
|
< 1 E-03
|
< 10 % of SIL 2 after T = 20 years
|
||
|
SFF
|
99%
|
|
||
|
Proof test interval T
|
20 years
|
Mission time
|
||
|
EN ISO 13849-1
|
Performance Level
|
d
|
|
|
|
Category
|
2
|
|||
|
MTTFavg
|
High
|
> 230 years
|
||
|
|
Mean diagnostic coverage DCavg
|
95%
|
||
Further data and information can be found in the corresponding project planning document in the "Electrical installation" chapter.