Calculation of the maximum response times
For the calculation of the response time to the request of a safety function, the overall system must be taken into account:
–
Response time of the connected safety sensors.
–
Input delay of the safety inputs.
–
Internal processing time.
–
Deceleration times, braking times, and stopping times from the parameterized safety functions.
–
When using a feedback system, the response time of encoder monitoring 0x2878:004
–
Safety bus:
–
Monitoring time for cyclic services.
–
Monitoring time in the safety PLC.
–
Processing time in the safety PLC
–
Delay times due to further components.
The ETG FSoE protocol specification contains formulas for calculating the maximum response time in fault-free operation and in the event of a fault.
In the "Application Knowledge Base", Lenze provides an Excel table as a calculation aid. This can be used to easily calculate the reaction times.
Please note the following:
The variables for the individual response times are named differently in the documentation for the c250-S safety controller than in the FSoE protocol specification of the ETG.
In the following graphics, the differences are marked with "Lenze" and "ETG".
|
Name Lenze
|
Name ETG
|
Description
|
Comment
|
|
T_Sensor
|
T_S
|
Processing time of the sensor until the signal is available at the interface.
|
See technical data of the sensor
|
|
T_InputFilter
|
|
Parameterized filter time of the safe input.
|
|
|
T_Input
|
T_I
|
Processing time of the safe input.
|
E.g. safety I/O module, FSoE sensor or inverter.
See technical data
|
|
T_WDInput
|
T_WD_In
|
Monitoring time parameterized in the safety PLC (c250-S) for the safe input module.
|
E.g. safety I/O module, FSoE sensor or inverter.
|
|
T_EtherCAT
|
T_Com
|
EtherCAT cycle time
|
|
|
T_FSoE
|
|
Processing time of the communication, depending on the EtherCAT cycle time
|
The documentation of the c250-S specifies max. 3 x T_EtherCAT.
The ETG FSoE protocol specification specifies max. 2 x T_Com.
It depends on the application which factor can be used. Factor 3 means improved availability of secure communications.
|
|
T_SafetyPLC
|
T_L
|
Processing time of the safety PLC (c250-S).
|
Corresponds to the set cycle time of the safety application.
|
|
T_Output
|
T_O
|
Processing time of the safe output.
|
E.g. safety I/O module or inverter.
See technical data
|
|
T_WDOutput
|
T_WD_Out
|
Monitoring time parameterized in the safety PLC (c250-S) for the safe output module.
|
E.g. safety I/O module or inverter.
|
|
T_Aktor
|
T_A
|
Processing time of the actuator.
|
See technical data of the actuator
|