Setting
Functional sequence and error response have no adjustable parameters.
 
Adapt the restart to your application.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2890
STO Source SD-In
–
Safety parameter (+Safety parameter list+)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
3
SD-In3
4
SD-In4
0x2891
STO Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x2892:001
STO: Restart
–
Safety parameter (+Safety parameter list+)
 
Restart behavior after the function has been canceled.
0
Acknowledged restart
1
Automatic restart
0x2893
STO "STO active" - Output
–
Safety parameter (+Safety parameter list+)
 
Selection of the safe output for the "STO active" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic