Motor/encoder travel ranges and cycle length

Linearly limited travel range
–
The travel range in the positive and negative direction is limited mechanically and on the software side by limit switches.
 
–
After travelling a defined distance, the drive returns in the opposite direction.
 
Fig. 1:  Spindle drive (linear axis)
Fig. 2: Position representation
1
Setting of the home position 
 
2
Position in the machine measuring system 
 
3
Position in the motor measuring system 
 
 
 
Unlimited travel range (Modulo)
–
The measuring system is repeated.
 
–
When the set cycle length is exceeded, a defined overflow takes place.
 
–
The cycle length corresponds to one revolution or tool distance of a turntable (end position = starting position).
 
–
Software limit switches are not active.
 
–
Absolute targets can be approached by exceeding the measuring system limit.
 
Fig. 3: Turntable
1
Cycle length (illustration = 60°) 
 
 
Fig. 4: Position representation
1
Cycle length 0x500A:031 
 
2
Position in the machine measuring system 
 
3
Position in the motor measuring system 
 
 
The kinematic parameters for the second encoder serve to define the conversion of an imported encoder position or encoder speed in machine units.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:030
Travel range
–
Setting can only be changed if the inverter is disabled.
 
Selection of the traversing range for the motor
0
Modulo
Unlimited traversing range (turntable). The cycle length must also be specified here.
1
Limited
Linearly limited traversing range (spindle drive).
0x500A:031
Cycle length
0.0001 ... [360.0000] ... 214748.3647
–
Setting can only be changed if the inverter is disabled.
 
The cycle length for an unlimited traversing range defines the position where the measuring system is repeated (position return to 0).
0x500B:030
Travel range
–
Setting can only be changed if the inverter is disabled.
 
Selection of the traversing range with regard to the encoder position.
0
Modulo
Unlimited traversing range (turntable). The cycle length must also be specified here.
1
Limited
Linearly limited traversing range (spindle drive).
0x500B:031
Cycle length
0.0001 ... [360.0000] ... 214748.3647
–
Setting can only be changed if the inverter is disabled.
 
The cycle length for an unlimited traversing range defines the position where the measuring system is repeated (position return to 0).