Interface
During a change-over, only the control and status words are switched. Depending on the technology application chosen, the bits of the respective control words and status words are already pre-assigned.
Assignment of control words and status words:
The following illustration shows the basic signal flow within the technology application and the change-over mechanism of the Interface selection parameter.
Fig. 1: Signal flow — Technology application
Control and status signals for fieldbus/system bus
The Interface selection parameter is used to select whether the technology application interface is to be controlled via the process data objects (control words) of the fieldbus or the system bus.
0x4001
0x4001–
In each case, 8 control words and 8 status words are provided, with a data width of 32 bits per word.
–
Depending on the setting in the Interface selection parameter, the status signals are also
written to the fieldbus or the system bus.
Parameter