Following error monitoring

The difference between the setpoint position and the actual position is the following error. The following error should be "0". If the position control is set optimally, only a minimal following error will occur. The following error is compensated dynamically and does not grow continuously.
However, certain processes impose a certain maximum limit in terms of the difference between the setpoint position and the actual position. If the limit is exceeded, it might be (for example) because of a failure to perform a movement within the machine, meaning that the system component does not reach the defined position at the relevant point in time. In such cases, it is appropriate to trigger an error response. The error response is adjustable. 0x500A:059
For diagnostic purposes, the current and maximum following error are displayed in the diagnostic parameter. 0x500A:058
 
Behaviour when the following error monitoring is active (0x500A:054 = activated)
 
Two following error limits can be parameterised.
Exceedance of following error limit 1 (0x500A:055):
–
A warning is displayed.
 
–
The current movement of the axis is not interrupted.
 
Exceedance of following error limit 2 (0x500A:056):
–
The set error response is executed. 0x500A:059
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:054
Following error monitoring
false
Inactive
true
Active
0x500A:055
Following error: Warning threshold
0.0000 ... [180.0000] ... 214748.3647
0x500A:056
Following error: Error threshold
0.0000 ... [360.0000] ... 214748.3647
0x500A:057
Actual following error
–
Read only
 
0x500A:058
Max. following error
–
Read only
 
0x500A:059
Response to following error
19
Fault > Application quick stop > Quick stop
20
Fault > Application quick stop > Quick stop
21
Fault> Application quick stop > Inverter disabled