Behaviour in the event of inverter disable

In standard cases, the setpoint position is compared against the actual position when the inverter is disabled. A position window can be used to control the automatic comparison between the setpoint position and actual position in the case of a disabled inverter. In the position window, positive and negative deviations can be set separately. If the distance between the last setpoint position before inverter disable and the current actual position is smaller than the parametrised value, the setpoint position keeps its last value. The setpoint position and the actual position will be compared upon exiting this window.
If the value is set to 0 units, the setpoint position is equated with the actual position in the case of an inverter disable. The limit value set for the upper and lower limits of the window in the parameters must not exceed the drift of the actual position at drive standstill plus an additional safety margin.
If higher values are set, the position controller makes a jerky compensation after the inverter is enabled. This is due to the existing system deviation.
Limit values:
 
Behaviour in case of an inverter disable during a movement
If the drive is disabled during a movement, for instance by the control word in the application or via the STO safety function, an error is triggered.
The Resp. to inverter disable during motion parameter can be used to set a different response. 0x500A:107
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:107
Response to inverter disable during operation
0
No response
2
Warning
19
Fault > Application quick stop > Quick stop
0x500A:136
Tolerance window actual position=set position upper limit
0.0000 ... [0.0000] ... 214748.3647
0x500A:137
Tolerance window actual position=set position lower limit
0.0000 ... [0.0000] ... 214748.3647