Server information modeling
PLCopen
The OPC UA Server can be configured via the »PLC Designer« with a standardized information model according to PLCopen. With this configuration PLC objects from the IEC 61131 application are published via OPC UA.
The configuration steps for the PLCopen information model can be found under PLCopen information model.
Array Expansion
The PLCopen information model represents IEC array elements as individual nodes. This array expansion is enabled [1] by default. It supports older Clients that don´t offer the feature of array complete access. If the Clients supports array complete access, the array expansion in setting parameter [0x2471:051] can be disabled [0] to reduce the complexity of the UA namespace and the memory consumption.
To get the setting active, a Server restart is necessary via the parameter [0x2470:001]. After the restart the active value is represented in the corresponding parameters [0x2472:051].
For further information how arrays are modeled, see Array IEC type mapping .
Resource utilization
The number of various IEC types, which should be represented in the automatically generated PLCopen namespace utilizes the resource.
When the percentage value of the resource utilization parameter [0x2473:052] approaches 100% the resource limit is reached. Use the controller logbook for detailed resource utilization information.
Counter measure is to reduce various variable types in the »PLC Designer« via the "Symbol Configuration". Make sure to publish only necessary variables for the use case and not complete function blocs with all their member variables.
For detailed information see Resource limitations.
User specific
From Controller Version V01.09. it is possible to load user specific information models.
The number of nodes and used companion specifications of the user specific information model utilizes the resource of the Controller.
When the percentage value of the resource utilization parameter [0x2473:053] approaches 100 % the resource limit is reached. Use the controller logbook for detailed resource utilization information.
Counter measure is to reduce the number of nodes and complexity of the user specific information model.