Server state, capabilities, resources

Server State

The Server State parameter [0x2473:001] provides the state of the Lenze OPC UA Server according to the OPC UA specification Part 5 - "ServerState".

Server Error

The Server Error parameter [0x2473:002] provides the current Lenze error code of the OPC UA Server. The error code and countermeasures are listed in chapter OPC UA Server error codes and countermeasures.

Controller logbook

The Lenze OPC UA server reports its states to the controller logbook, which can be accessed via Lenze engineering tools such as EASY Starter or -PLC Designer-.

OPC UA Server error codes and countermeasures

The Lenze OPC UA Server can send the following messages to the controller logbook. Further notes on the error and corrective measures are described here.

ErrorCode

Description

     

0x1301

Error

Out of memory

Cause

Not enough memory

Remedy

 

Reduce the number of symbols in the symbol configuration in the PLC Designer. Further information about the handling of required resources for the PLCopen namespace can be found in chapter Resource limitations.

0x1302

Error

Failed to update address space

Cause

The address area "PLCopen" could not be updated

Remedy

Reduce the number of symbols in the symbol configuration in the PLC Designer. Further information about the handling of required resources for the PLCopen namespace can be found in chapter 2.2.3 can be found Resource limitations.

0x1303

Error

Internal error

Cause

An internal operation has failed

- Firmware / server configuration inconsistent

- Hardware error

- RAM/ internal flash memory not sufficient

- Configuration or certificate data not valid

- PLC project or runtime dependency, if applicable

Remedy

Device restart / Update device firmware / Contact support and have trace created

0x1304

Error

Node set file %s could not be found

Cause

Referenced Nodeset file can-t be found.

Remedy

Nodeset file must be stored under /sdcard/plc/prg/pta/opc_ua_server/

Check Nodeset file name in Mapping file.

0x1305

Error

Mapping file at line %s, column %s is erroneous

Cause

Content of Mapping file is invalid.

Remedy

Check mapping information in mapping file.

0x1306

Error

Mapping file includes more nodesets than supported

Cause

The mapping file configures more nodesets than are supported.

Remedy

Reduce the number of nodesets according to chapter OPC UA Server capabilities.

0x1201

Warning

Update of address space is incomplete

Cause

The address area e.g. "PLCopen" is incomplete

Remedy

Reduce the number of symbols in the symbol configuration in the -PLC Designer-. Further information about the handling of required resources for the PLCopen namespace can be found in chapter Resource limitations.

0x1202

Warning

Client user authentification failed

Cause

Client user authentication has failed.

Remedy

Check user administration within PLC Designer (check existence of user and its password).

Are the OPC UA client credentials correct?

0x1203

Warning

Client (%s) operation %s failed with status code %s

Cause

The client (e.g. urn:CDE279763:UnifiedAutomation:UaExpert) operation "Read" failed with status code e.g. "BAD_NODEID_UNKNOWN".

Remedy

Check existence of nodes and client rights.

PLC project W Check symbol configuration and PLC status

0x1204

Warning

Too many Client requests on subsystem %s

Cause

The subsystem cannot handle all client requests.

Remedy

Check client interaction (check session count or access frequency).

DOS attack?

0x1205

Warning

Client access denied on subsystem %s

Cause

Unauthorized access to parts of the information model was detected and denied.

Remedy

Check client rights.

Match with error code "Client Operation Failed" 0x1203

0x1206

Warning

Client has been rejected because the certificate is not trusted

Cause

Client connection was rejected by the server due to untrusted client certificate.

Remedy

Open PLC Designer security screen and check certificates.

Trust or update the client certificate.

0x1207

Warning

Needed %s element for mapping of %s is missing or erroneous.

Cause

The mapping file contains incorrect entries (e.g. missing elements that are needed, wrong values like data type or NodeId).

Remedy

Correct mapping file and add/correct missing element.

0x1208

Warning

Namespace-ID for namespace-uri %s could not be found

Cause

The namespace uri for a mapping element is incorrect and cannot be mapped to the server's namespaces.

Remedy

Check and correct namespace uri

0x1209

Warning

 

Nodeid for csv name %s could not be found

Cause

The placeholder keyword for the nodeid is incorrect and could not be found.

Remedy

Check placeholder keyword or update CSV file.

0x1210

Warning

Nodeid %s of element %s not valid

Cause

The NodeId is either empty or has an incorrect value that does not comply with the Opc Ua specification (e.g. wrong identifier type).

Remedy

Check NodeId and align with the Nodeset.

0x1211

Warning

Element % is missing for mapping of %s. Skipping element

Cause

The mapping file contains a mapping element where the ParameterElement or VariableElement is missing.

Remedy

Correct mapping file and add missing element.

0x1212

Warning

CSV-File %s could not be found

Cause

Referenced csv file can-t be found.

Remedy

csv file must be stored under /sdcard/plc/prg/pta/opc_ua_server/

Check csv file name in mapping file.

0x1213

Warning

CSV-File %s at line %s is errornous

Cause

The CSV format of the CSV file is incorrect.

Remedy

Check CSV file again.

0x1214

Warning

Namecollision for %s in csv file %s

Cause

There are several entries with the same name in the CSV file.

Remedy

Fix name collision.

0x1215

Warning

The arguments of the node %s of the Mappingfile do not match the arguments of the nodeset file. Skipping element

Cause

Replace first argument with placeholder if necessary (methodargument, eventargument).

The mapping file does not match the nodesets. Maybe different versions were used where the arguments do not match.

Remedy

Align mapping file and nodeset file and check methods/events

0x1216

Warning

The notifier %s for the node %s could not be found. Setting notifier to server node

Cause

The NodeId of the notifier could not be found in the nodeset.

Remedy

Synchronize mapping file and nodeset files and check OptionalPlaceholder/Events

0x1217

Warning

The method %s was called again, before the current execution was finalised

Cause

A mapped method was called again before the first call was completed.

Remedy

Wait until method has been finalized. Increase client timeout if necessary.

0x1218

Warning

Out of memory (%s)

Cause

Not enough memory

Remedy

Reduce number of sessions, monitored items, -

0x1219

Warning

Internal warning (%s)

Cause

An internal operation has failed.

Remedy

-

0x1401

Info

Started on %s

Cause

Server was started successfully.

Remedy

-

0x1402

Info

Is shutting down

Cause

Server is shut down.

Remedy

  • Device restart.

  • Update device firmware.

  • Contact support. Create trace.

0x1403

Info

Certificate store changed

Cause

The certificate store has been updated.

Remedy

-

0x1404

Info

User database changed

Cause

The user database has been updated.

Remedy

-

0x1405

Info

Client %s connected

Cause

Client (e.g. urn:CDE279763:UnifiedAutomation:UaExpert) has connected to server.

Remedy

-

0x1406

Info

Client %s disconnected

Cause

Client (e.g. urn:CDE279763:UnifiedAutomation:UaExpert) has disconnected from the server.

Remedy

-

0x1407

Info

Client %s rejected

Cause

Client (e.g. urn:CDE279763:UnifiedAutomation:UaExpert) was rejected by the server.

Remedy

The client connection was rejected, due to the occupied session count (all reserved sessions are in use).

0x1408

Info

Address space %s changed

Cause

The address area, e. g. "PLCopen" has been changed.

Remedy

-

0x1409

Info

The mapping was loaded. %s elements have been skipped due to mapping errors.

Cause

The mapping was loaded. X Elements were skipped due to mapping errors

Remedy

-

0x1410

Info

No nodeset files are specified in mapping file. Disabling provider.

Cause

No nodeset files were specified in the mapping file. The provider is disabled.

Remedy

-

Subscriptions and monitored items

As a server utilization indication, Lenze parameters are available for-

  • maximum [0x2472:011] and used [0x2473:011] number of subscriptions and

  • maximum [0x2472:012] and used [0x2473:011] number of monitored items.

Publishing and sampling intervall

In case of performance problems, the minimum possible publishing and sampling interval can be increased. For this purpose, following Lenze parameter setting parameters are available-

  • minimum publishing interval [0x2471:013]

  • minimum sampling interval [0x2471:014]

Expert settings

For certain applications, it may be helpful to adapt the server’s basic configuration with regard to capabilities and resource management. Certain configurations can be enabled using the parameter Expert setting [0x2471:200]:

  • resource-quota [0x2471:200 bit0] - If this bit is set, the request-buffer limitation is active per session.This guarantees a certain number of requests for every possible session. If this bit is not set, a request- buffer limitation is active over all sessions. In this case all the sessions share the memory pool.

  • reserved [0x2471:200 bit1-15]

To get the settings active, a Server restart is necessary via the parameter [0x2470:001]. After the restart the active values are represented in the corresponding parameters [0x2472:013] and [0x2472:014].