Process data transfer

The process data interface is determined by the EtherCAT device via the number and type of modules inserted into the slots.
For the compilation of the process data, modules with the same name are available for the EtherCAT device and the EtherCAT slave:
Module
Info
Mixed In / Out Word 0002
Rx and Tx process data object, each with 2 words (RxPDO 4 bytes, TxPDO 4 bytes)
Mixed In / Out Word 0004
Rx and Tx process data object, each with 4 words (RxPDO 8 bytes, TxPDO 8 bytes)
Mixed In / Out Word 0008
Rx and Tx process data object, each with 8 words (RxPDO 16 bytes, TxPDO 16 bytes)
Mixed In / Out Word 0016
Rx and Tx process data object, each with 16 words (RxPDO 32 bytes, TxPDO 32 bytes)
Mixed In / Out Word 0032
Rx and Tx process data object, each with 32 words (RxPDO 64 bytes, TxPDO 64 bytes)
Mixed In / Out Word 0064
Rx and Tx process data object, each with 64 words (RxPDO 128 bytes, TxPDO 128 bytes)
Mixed In / Out Word 0096
Rx and Tx process data object, each with 96 words (RxPDO 192 bytes, TxPDO 192 bytes)
 
The length of the process data is 2 ... 96 words (max. 32 PDO and max. 512 words per direction).