EtherCAT I/O mapping status
In addition to the actual I/O mapping of the process data, the EtherCAT device also has input and output channels in which additional information is supplied for the PLC application.
This information can be accessed directly from the PLC code.
|
Name
|
Info
|
|
Configuration valid
|
RO/BOOL
Indicates whether the currently active configuration is valid.
FALSE: There is no valid configuration.
TRUE: Configuration is valid.
A configuration consists both of a component from the slave application (EtherCAT device) and a component of the configuration from the EtherCAT master. These must match.
|
|
EtherCAT state
|
RO/UINT
Specifies the current EtherCAT status of the slave.
0: No EtherCAT module
1: Initialization
2: Pre-Operational
3: Bootstrap
4: Safe-Operational
8: "Operational"
|
|
Process data valid
|
RO/BOOL
This flag indicates whether the process data is valid.
FALSE: The process data is not valid.
TRUE: The process data is current and valid.
|
|
Watchdog error
|
RO/BOOL
This flag indicates whether there is a SyncManager watchdog error.
FALSE: No SyncManager watchdog error.
TRUE: The SyncManager watchdog was triggered.
The value of the watchdog is set by the configuration tool of the EtherCAT master.
|