Commissioning

For commissioning a control unit with an EtherCAT device located in a lower-level EtherCAT network, it is necessary to perform a custom configuration of the master and the device.
Both configurations must be represented identically on the master control unit (e.g., using the software TwinCAT 3.x
®
from Beckhoff) and the slave control unit (with the engineering tool "PLC Designer" from Lenze). Failure to do so will render a transition to the "Operational" status impossible.
 
Configuration of the EtherCAT device using the "PLC Designer"
The term "EtherCAT device" is used to describe the EtherCAT slave interface of the slave control unit. The EtherCAT device specifies the process image which needs to be reproduced identically in the master configuration for the EtherCAT slave.
How to integrate EtherCAT devices in the control configuration:
1.
Select the "Add device" command in the context menu of the target system (device, Lenze controller, etc.) to extend the control configuration with the EtherCAT device.
The EtherCAT device is located in the category under /Fieldbusses/EtherCAT/Slave/EtherCAT-Device
 
2.
Name the inserted EtherCAT device sensibly.
You can enter a name by clicking on the element. The designations must only contain the characters "A ... Z", "a ... z", "0 ... 9", or "_" and must not begin with a digit.
 
3.
Go to the context menu of the EtherCAT device and execute the "Add device" command.
 
4.
In the dialog box that appears, select the I/O modules to be used for the EtherCAT device and add them to the EtherCAT device by clicking the "Add device" button. The structure of the process image is defined via the modules.
 
5.
In the tab for the module, define the variables for the IO signals.
 
The control configuration of the EtherCAT device in the "PLC Designer" is completed.
Continue with the control configuration of the EtherCAT slave; see EtherCAT-Slave configuration in Beckhoff TwinCAT 3.x® .