Error messages
|
Error message
|
Error type
|
Description
|
|
MMC - address assignment - done
|
Info
|
The address assignment has been completed successfully.
|
|
MMC - address assignment - invalid device on position ... (..._.../..._...)
|
ERROR
|
During the address assignment by means of the ADDR_ASSIGNMENT_EXTERNALLY or ADDR_ASSIGNMENT_CONFIG_SLAVEORDER service, a slave has been detected unexpectedly at the given position.
|
|
MMC - address assignment - less slaves connected (...) than configured (...)
|
ERROR
|
During the address assignment, less slaves are connected to the physical EtherCAT bus than specified in the active configuration.
|
|
MMC - address assignment - more slaves connected than configured
|
ERROR
|
During the address assignment, more slaves are connected to the physical EtherCAT bus than specified in the active configuration.
|
|
MMC - address assignment - writing address ... at position ... by CoE ... (error ...)
|
ERROR
|
During the address assignment, an error has occurred for the slave at the given position. For further information see general error codes (L_ETC_ERRORCODE).
|
|
MMC - address assignment - writing address ... at position ... failed (error ...)
|
ERROR
|
During the address assignment, an error has occurred for the slave at the given position. For further information see general error codes (L_ETC_ERRORCODE).
|
|
MMC - address assignment - written address ... at position ... successfully
|
Info
|
The address has been successfully assigned to the slave at the given position.
|
|
MMC - devices not ascending or device(s) missing at line ... (...)
|
ERROR
|
In the "mmc-0-conf.csv" configuration file, the slaves are not specified in ascending order (starting with ’1001’) or are missing. Or the address space is incomplete.
|
|
MMC - duplicated alias address ... at positions ... and ...
|
ERROR
|
While the EtherCAT bus was booted and the slaves were checked, several slaves were found with identical "Second Station Address" (alias address) at the given position. The first slave behind the EtherCAT master has the position ’1’.
|
|
MMC - Error in configuration files
|
ERROR
|
Errors were detected during the analysis of the "mmc-0-conf.csv" configuration file or the "mmc-0-ident.csv" identification file. Additional information about the error is displayed in the logbook further above.
|
|
MMC - file does not exist ...
|
Info
|
The "mmc-0-conf.csv" configuration file or the "mmc-0-ident.csv" identification file have not been found in the directory .../USBStorage/IPC/PLC or .../SDCard/IPC/PLC. As both files do not have to be available in the system (depending on the service), this merely serves as information.
|
|
MMC - Internal error (...)
|
ERROR
|
An internal error has occurred. The internal error number is output in the error message. Please contact Lenze customer service!
|
|
MMC - invalid alias address ... at position ... (.../.../.../...)
|
ERROR
|
While the EtherCAT bus was booted and the slaves were checked, a slave with an invalid or unexpected "Second Station Address" (alias address) was detected at the specified position. The first slave behind the EtherCAT master has the position ’1’. Parameters in parentheses: Vendor-ID/Product Code/Revision/Serial Number.
|
|
MMC - invalid configuration
|
ERROR
|
An action has been aborted because no valid configuration is active.
|
|
MMC - mandatory slave ... is not present
|
ERROR
|
While the EtherCAT bus was booted and the slaves were checked, a mandatory slave was not found at the bus. In the error message, the EtherCAT address or "Second Station Address" (alias address) of the slave is given.
|
|
MMC - 'Modular Machine Configuration' is active - EtherCAT Master is controlled by L_ETC_MMCController
|
Info
|
The L_ETC_MMCController function block is used in the PLC program. The behavior of the EtherCAT master is controlled by the function block.
|
|
MMC - no configuration checks
|
Info
|
While the EtherCAT bus is booted, the configuration is not checked because the RUN_WITHOUT_CHECK service is active.
|
|
MMC - no valid service active
|
ERROR
|
When using the L_ETC_MMCController function block, there was an attempt made to boot the EtherCAT bus (xRestart = TRUE). But no service is active.
|
|
MMC - number of device in device tree differs at line ... (...)
|
WARNING
|
The number of slaves from the "mmc-0-conf.csv" configuration file is greater than defined in the »PLC Designer« project. This is a warning because the excessive devices from the configuration are simply ignored.
|
|
MMC - optional slave ... is present, but not allowed
|
ERROR
|
While the EtherCAT bus was booted with the RUN_OPTIONAL_SLAVES_PROHIBITED service active, a "non-mandatory" slave was found.
|
|
MMC - parsing error at line ... (...)
|
ERROR
|
Errors were detected in the specified line number during the analysis of the "mmc-0-conf.csv" configuration file or the "mmc-0-ident.csv" identification file. The line number starts with ’1’.
|
|
MMC - parsing file succeeded ...
|
Info
|
The specified "mmc-0-conf.csv" configuration file or the "mmc-0-ident.csv" identification file have been analyzed without any errors.
|
|
MMC - service ... started, configuration '...'
|
Info
|
A service has been started with the given configuration.
|
|
MMC - service stopped
|
Info
|
A service has been stopped by the user via the L_ETC_MMCController function block or via a reset.
|
|
MMC - slave ... ident data failed - CoE ... (set .../act ...)
|
ERROR
|
The expected and current parameter contents do not match. An error occurred in the specified slave while the EtherCAT bus booted and the additional identification parameters from the "mmc-0-ident.csv" configuration file were checked.
|
|
MMC - slave ... ident failed - CoE ... (error ...)
|
ERROR
|
An error occurred in the specified slave while the EtherCAT bus booted and the additional identification parameters from the "mmc-0-ident.csv" configuration file were checked. For further information see general error codes (L_ETC_ERRORCODE).
|
|
Modular machine configuration: Only one instance of L_ETC_MMCController allowed!
|
ERROR
|
This message is transmitted when the EtherCAT master configuration is generated if more than one instance of the L_ETC_MMCController function block is used in the application. Please note: An instance might also have been created in a library!
|